Chapter 2 · Lesson 4 of 5
Using electrical meters correctly
1 min read
Each electrical measurement has its own connection. Voltage is a difference in potential between two points, so the leads go in parallel across the load while the circuit is live; with the disconnect open you simply read zero.
Resistance is measured with power off, because the ohmmeter supplies its own small current and outside voltage gives false readings and can damage the meter. Current is measured with a clamp around a single conductor.
| Symptom | Cause | Fix |
|---|---|---|
| Coil reads lower ohms than expected | Parallel parts still wired in | Disconnect one lead to isolate it |
| Clamp on a whole cord reads near zero | Supply and return fields cancel | Clamp one conductor or use a line splitter |
| Odd readings on an ECM or inverter unit | Waveform is not a clean sine wave | Use a true-RMS meter |
An averaging meter assumes a sine wave, so it can be well off on the chopped waveforms of electronically commutated motors and variable-frequency drives. Also check the function setting: reading a 24-volt AC control circuit on the DC volts setting gives a meaningless number.
Check yourself
1. A clamp-on ammeter placed around the entire two-conductor cord of an operating appliance reads approximately zero. What is the explanation?
2. An ohmmeter placed across a relay coil that is still wired into the control circuit shows a resistance lower than the coil's expected value. What is the most likely cause?