Transformers, single-phase and three-phase power
1 min read
A transformer works by mutual induction, which needs a magnetic field that keeps building and collapsing. Only alternating current does that. On steady DC, nothing is induced in the secondary and the primary, limited only by its low winding resistance, overheats.
The VA rating sets how much current the secondary can supply, so check it before adding relays, zone dampers or valves to an existing control circuit.
A single-phase service usually has a center-tapped secondary. You read the full voltage, often 240, between the two hot legs and half of it, often 120, from either leg to the grounded center tap, the neutral. Voltage is always stated between two named conductors, which also applies to three-phase line-to-line and line-to-neutral readings.
- A three-phase motor's rotation is set by phase order, so swapping any two line leads reverses it. It has no start winding or capacitor to swap.
- If one leg is lost while running, the motor keeps turning but current on the other two legs climbs and the windings overheat. A stopped motor cannot start on two legs.
Example: a 50 VA, 24-volt transformer can supply about 2.1 amps.
If the existing coils and board already draw 1.5 amps and you add a zone damper that draws 0.9 amps, the total of 2.4 amps is more than the transformer can carry, so it will overheat or open its fuse. Use a larger transformer or a separate one for the new load.
Check yourself
1. After a compressor change-out, a three-phase condenser fan motor is turning backward. What is the correct correction?
2. A technician asks whether a DC power supply can be used on the primary of a control transformer for a bench test. What is the correct answer?