Airflow, static pressure and capacity
1 min read
In a duct, total pressure equals static pressure plus velocity pressure. Static pressure pushes outward on the duct walls in every direction. Velocity pressure exists only because the air is moving and is sensed facing into the stream.
A blower delivers less air as the resistance against it rises, which is what a fan curve shows. A loaded filter, an undersized return or furniture over the only return grille all raise static pressure and cut airflow.
- Less air across a cooling coil makes the coil colder, cuts capacity, and in severe cases freezes the coil.
- Raising blower speed warms the coil and shifts capacity toward sensible cooling, which makes humidity control worse, not better.
Airflow can be estimated from temperature rise with CFM = BTU/h ÷ (1.08 × ΔT), where ΔT is the supply temperature minus the return temperature.
Example: a furnace delivering 54,000 BTU/h of heat with a 50°F rise is moving 54,000 ÷ (1.08 × 50) = 1,000 CFM. If the rise climbs with the same heat output, airflow has dropped, so look for a dirty filter, a closed return or a restriction.
Check yourself
1. On a system with a fixed-speed blower, a technician finds a heavily loaded filter and an undersized return, and measures an unusually high external static pressure. What is happening to airflow and to capacity?
2. A homeowner has pushed a sofa against the only return grille and keeps the bedroom doors closed against undercut-free thresholds. What happens to the cooling system?