Airside, static pressure and condensate problems
1 min read
Total external static pressure is the supply-side reading plus the return-side reading, taken without regard to sign. It tells you a restriction exists but not where. Example: an air handler rated for 0.5 in. w.c. shows 0.35 in. w.c. on the supply side and 0.55 in. w.c. on the return side, for 0.90 in. w.c. total.
Most of the excess is on the return, so measure the drop across the filter, the return grille and the return duct to find the culprit. Raising blower speed or adding refrigerant does not fix an airside problem.
- A pan that overflows only while the blower runs on a draw-through unit points to a missing or too-shallow trap.
- Water in the secondary pan means the primary drain failed. Restore any jumpered float switch, clear the drain, and test that the switch stops the system.
- A boom at blower start and stop, with normal refrigerant readings, is a flat duct panel flexing. Brace or cross-break the panel.
Duct noise is diagnosed the same way: match the symptom to its timing. A sound tied exactly to blower start and stop comes from the change in duct pressure, while refrigerant-side noise such as liquid slugging would also show up in abnormal pressures and temperatures.
Check yourself
1. The installation instructions on an air handler state a maximum total external static pressure of 0.5 in. w.c. The technician measures 0.95 in. w.c. total external static, with most of the reading appearing on the return side of the blower. What is the correct next diagnostic step?
2. A homeowner complains of a loud booming sound from the supply plenum each time the blower starts and each time it stops. Refrigerant pressures, superheat, subcooling and blower amp draw are all normal. What is the most likely cause?