Quibank app: now on the App Store — free, works offline. Get the app ↗

Chapters0/29 ▾
  1. 1.Safety0/4
    1. Lockout, tagout and stored electrical energy
    2. Refrigerant, cylinders and pressure hazards
    3. Carbon monoxide and combustion hazards
    4. PPE, brazing and job-site hazards
  2. 2.Tools & Measurement0/5
    1. Measuring temperature and proving the thermometer
    2. Humidity, wet bulb and dew point
    3. Gauge pressure, absolute pressure and vacuum
    4. Using electrical meters correctly
    5. Airflow, leak detection and charging tools
  3. 3.Basic Electrical0/4
    1. Ohm's law, power and power factor
    2. Series, parallel and reading a ladder diagram
    3. Transformers, single-phase and three-phase power
    4. Single-phase motors, capacitors and winding tests
  4. 4.Science & Refrigeration Cycle0/4
    1. Heat, sensible and latent heat, and heat transfer
    2. Saturation and the four main components
    3. Calculating superheat and subcooling
    4. Metering devices and reading the charge
  5. 5.Construction, Comfort & Airflow0/4
    1. The building envelope: insulation, air sealing and windows
    2. Loads, equipment sizing and comfort
    3. Airflow, static pressure and capacity
    4. Duct leakage, noise, filters and ventilation
  6. 6.AC Components & Operation0/4
    1. Compressors and keeping liquid out
    2. Outdoor coil, indoor coil and condensate
    3. Metering devices, the TXV bulb and charging method
    4. Line sets, accessories, service valves and thermostats
  7. 7.AC Diagnosis & Service0/4
    1. Reading superheat and subcooling patterns
    2. Troubleshooting the control circuit
    3. Compressor electrical faults
    4. Airside, static pressure and condensate problems
Saved in this browser. Move it to another device →
← AC Diagnosis & Service

Chapter 7 · Lesson 4 of 4

Airside, static pressure and condensate problems

1 min read

Total external static pressure is the supply-side reading plus the return-side reading, taken without regard to sign. It tells you a restriction exists but not where. Example: an air handler rated for 0.5 in. w.c. shows 0.35 in. w.c. on the supply side and 0.55 in. w.c. on the return side, for 0.90 in. w.c. total.

Most of the excess is on the return, so measure the drop across the filter, the return grille and the return duct to find the culprit. Raising blower speed or adding refrigerant does not fix an airside problem.

  • A pan that overflows only while the blower runs on a draw-through unit points to a missing or too-shallow trap.
  • Water in the secondary pan means the primary drain failed. Restore any jumpered float switch, clear the drain, and test that the switch stops the system.
  • A boom at blower start and stop, with normal refrigerant readings, is a flat duct panel flexing. Brace or cross-break the panel.

Duct noise is diagnosed the same way: match the symptom to its timing. A sound tied exactly to blower start and stop comes from the change in duct pressure, while refrigerant-side noise such as liquid slugging would also show up in abnormal pressures and temperatures.

Check yourself

1. The installation instructions on an air handler state a maximum total external static pressure of 0.5 in. w.c. The technician measures 0.95 in. w.c. total external static, with most of the reading appearing on the return side of the blower. What is the correct next diagnostic step?

2. A homeowner complains of a loud booming sound from the supply plenum each time the blower starts and each time it stops. Refrigerant pressures, superheat, subcooling and blower amp draw are all normal. What is the most likely cause?