Superheat is heat added to vapor after all the liquid has boiled. Subcooling is heat removed from liquid after all the vapor has condensed. Both start with a pressure reading converted to a saturation temperature on a pressure-temperature chart, compared with a line temperature taken at the same point.
Never add the two numbers together. Any measurable superheat proves the refrigerant leaving the coil is all vapor, which is what protects the compressor.
| Reading | Formula | Example |
|---|---|---|
| Superheat (suction line) | Line temperature minus saturation temperature | 55°F minus 45°F = 10°F |
| Subcooling (liquid line) | Saturation temperature minus line temperature | 105°F minus 95°F = 10°F |
- Zero superheat means boiling is not finished, so liquid can flood back to the compressor.
- Subcooling proves a solid column of liquid, not a mix with bubbles, is feeding the metering device.
- Evaporator superheat is read at the coil outlet; total superheat at the compressor inlet is normally higher because the suction line picks up heat.
- For a zeotropic blend with glide, use the dew point for superheat and the bubble point for subcooling.
Check yourself
1. A liquid-line pressure corresponds to a saturation temperature of 110°F, and the liquid line at the same point measures 98°F. Which statement is correct?
2. A technician reads a suction pressure whose saturation temperature is 40°F, and measures the suction line at that same point at 52°F. What is the correct interpretation?