Chapters0/29 ▾
Chapter 6 · Lesson 1 of 4
Compressors and keeping liquid out
1 min read
A reciprocating compressor uses pistons with suction and discharge reed valves. A scroll compressor traps gas between a fixed scroll and an orbiting scroll and squeezes it continuously toward the center, so it needs no reed valves, runs smoother and tolerates small amounts of liquid better.
Either way, a compressor is built to pump vapor. Liquid does not compress, so a slug of it puts huge force on valves, pistons and scroll flanks, and liquid refrigerant also washes the oil off bearings.
| Part | Where | Job |
|---|---|---|
| Crankcase heater | On the compressor | Keeps oil warm during the off cycle so refrigerant does not migrate into it |
| Accumulator | Suction line, low side | Traps liquid leaving the evaporator and meters oil back through a small hole |
| Receiver | Liquid line, high side | Stores surplus liquid for a variable charge |
Example: a heat-pump compressor sits in a cold yard all night. Refrigerant migrates to the coldest place and dissolves into the oil. Without a working crankcase heater, the oil foams at start-up and the compressor loses lubrication.
Check yourself
1. A suction-line accumulator is installed on a split system. How does it protect the compressor during normal operation?
2. Why is liquid refrigerant that reaches the compressor cylinder or scroll set destructive?
Facts checked 2026-11-15 · Sources: NATE: Certification exams