Chapter 4 · Lesson 2 of 4
Saturation and the four main components
1 min read
When liquid and vapor of a pure refrigerant are present together, the refrigerant is saturated, and its pressure and temperature are locked together. Each saturation pressure matches exactly one temperature, and raising the pressure raises the boiling point.
The cycle is built on that fact. The compressor raises pressure so the refrigerant will condense at a temperature above the outdoor air. The metering device drops pressure so the refrigerant will boil at a temperature below the indoor air.
- Evaporator: low-pressure liquid absorbs heat from the air and boils into vapor.
- Compressor: a vapor pump that raises pressure and temperature. Liquid does not compress and can break valves.
- Condenser: hot vapor gives up heat to outdoor air and condenses into liquid.
- Metering device: throttles the liquid to a low pressure. It and the compressor divide the high side from the low side.
The condenser always rejects more heat than the evaporator absorbs, because it must also shed the heat of compression added by the compressor's work. Example: if an evaporator picks up heat from a house, the outdoor coil has to get rid of that heat plus the energy the compressor added, so condensers are sized for more than the evaporator load.
Check yourself
1. Which two components divide a mechanical refrigeration system into its high-pressure side and its low-pressure side?
2. For a pure refrigerant sitting at saturation, with liquid and vapor present together, what is the relationship between pressure and temperature?