NATE HVAC Cheat Sheet: Key Facts

Every key takeaway and common trap from the NATE HVAC study guide on one page, grouped by chapter. Tap a lesson link to read the full explanation.

48 facts · 7 chaptersFacts checked 2026-11-15
  1. Safety
  2. Tools & Measurement
  3. Basic Electrical
  4. Science & Refrigeration Cycle
  5. Construction, Comfort & Airflow
  6. AC Components & Operation
  7. AC Diagnosis & Service

Chapter 1

Safety

Key takeaways

Common trap

  • Wrong answers often offer a shortcut that sounds careful: working live with one hand in a pocket, using leather gloves as insulation, or letting a lead technician lock out for the whole crew. If the job can be done de-energized, the answer is to de-energize, lock out and verify. → Lockout, tagout and stored electrical energy
  • Distractors treat a combustion defect as a comfort or efficiency issue: seal the crack with high-temperature sealant, raise the blower speed to dilute the leak, or leave the furnace running until the owner schedules a replacement. Any defect that can put flue gas into the living space means the appliance comes out of service now. → Carbon monoxide and combustion hazards

Quick reference

Refrigerant, cylinders and pressure hazards →
SituationHazardSafe practice
Charging cylinder transfers slowlyFlame spikes pressure and softens steelGentle warming such as a warm-water bath, within the marked limit
Filling a recovery cylinderLiquid expands with heat and has no roomFill by weight on a scale and keep a vapor space
Large leak in a basementVapor is heavier than air and displaces oxygenVentilate and test the air before entering

Chapter 2

Tools & Measurement

Key takeaways

Common trap

  • Wrong answers offer signs that feel convincing but prove nothing: cold hoses, a change in pump sound, or one low micron reading while the pump is still running. A vacuum is proven only by isolating the system and seeing the reading hold. → Gauge pressure, absolute pressure and vacuum

Quick reference

Using electrical meters correctly →
SymptomCauseFix
Coil reads lower ohms than expectedParallel parts still wired inDisconnect one lead to isolate it
Clamp on a whole cord reads near zeroSupply and return fields cancelClamp one conductor or use a line splitter
Odd readings on an ECM or inverter unitWaveform is not a clean sine waveUse a true-RMS meter

Chapter 3

Basic Electrical

Key takeaways

Common trap

  • Distractors for these questions are usually the right digits in the wrong place: multiplying when you should divide, or moving the decimal point. Before choosing, check the size: a 240-volt heater drawing 12 amps cannot have 2,880 ohms of resistance. → Ohm's law, power and power factor

Quick reference

Ohm's law, power and power factor →
Known readingsFormulaResult
240 V across a heater, 12 A through itR = E ÷ I20 ohms
3,600 W element at 240 VI = P ÷ E15 amps
Transformer rated 75 VA, 24 V secondaryI = VA ÷ VAbout 3.1 amps

Chapter 4

Science & Refrigeration Cycle

Key takeaways

Common trap

  • Expect distractors that add the two temperatures, call the saturation temperature itself the superheat, or swap the words superheat and subcooling. Superheat belongs to vapor on the suction side and subcooling belongs to liquid on the liquid line. → Calculating superheat and subcooling
  • Distractors often reverse the metering logic: they claim a TXV closes down when the load rises, that a fixed orifice adjusts itself, or that TXV systems are charged by superheat. A TXV opens further on a rising load to hold its superheat, and that steady superheat is exactly why it cannot tell you the charge. → Metering devices and reading the charge

Quick reference

Heat, sensible and latent heat, and heat transfer →
TermMeaningHVAC example
Sensible heatChanges temperature, no change of stateLowering room dry-bulb temperature
Latent heatChanges state, no temperature changeCondensing water vapor on the coil
ConductionHeat moves by direct contactA clamp-on probe on copper
ConvectionA moving fluid carries heatAir blown across a coil
RadiationEnergy travels as waves, no medium neededAn infrared thermometer reading a surface
Calculating superheat and subcooling →
ReadingFormulaExample
Superheat (suction line)Line temperature minus saturation temperature55°F minus 45°F = 10°F
Subcooling (liquid line)Saturation temperature minus line temperature105°F minus 95°F = 10°F

Chapter 5

Construction, Comfort & Airflow

Key takeaways

Common trap

  • Wrong answers treat insulation as the fix for everything: pile more batts over an open hatch, or fill the cavity so condensation cannot happen. More insulation does not stop air leaks, and moist air still condenses on any surface below its dew point. → The building envelope: insulation, air sealing and windows
  • A common wrong answer says a restriction makes the blower work harder and move more air, or that higher static pressure only shows the blower is doing its job. On a fixed-speed blower, more resistance always means less air and less delivered capacity. → Airflow, static pressure and capacity
  • Watch for answers that fix one symptom by hurting the whole system: slowing the blower for the whole house to quiet one register, or choking a balancing damper until the noise stops. Fix the branch, the filter area or the leak where the problem actually is. → Duct leakage, noise, filters and ventilation

Chapter 6

AC Components & Operation

Key takeaways

Common trap

  • Do not mix up the accumulator and the receiver. The accumulator is on the low side and protects the compressor from liquid; the receiver is on the high side and stores liquid. Neither one filters acid or moisture; that is the filter-drier's job. → Compressors and keeping liquid out
  • Distractors often claim a condensate trap stops refrigerant from escaping, or that a float switch only sounds an alarm or bypasses water to keep the system running. The trap blocks air drawn in by negative pressure, and the float switch opens the control circuit so the system stops making water. → Outdoor coil, indoor coil and condensate

Quick reference

Compressors and keeping liquid out →
PartWhereJob
Crankcase heaterOn the compressorKeeps oil warm during the off cycle so refrigerant does not migrate into it
AccumulatorSuction line, low sideTraps liquid leaving the evaporator and meters oil back through a small hole
ReceiverLiquid line, high sideStores surplus liquid for a variable charge

Chapter 7

AC Diagnosis & Service

Key takeaways

Common trap

  • Expect an answer that simply adds refrigerant whenever suction pressure is low. Low suction comes from undercharge, restriction and low airflow alike, and adding refrigerant to a restricted or airflow-starved system overcharges it. Even a true undercharge calls for finding and repairing the leak first. → Reading superheat and subcooling patterns
  • Never pick an answer that jumpers, bypasses or resets a safety without fixing the cause, or that installs larger fuses to keep a unit on line. Safety controls and overcurrent devices report real faults; removing them only removes the protection. → Troubleshooting the control circuit

Quick reference

Reading superheat and subcooling patterns →
PatternLikely fault
High superheat, low subcooling, low pressuresUndercharge from a leak; find and fix the leak
High superheat, high subcooling, temperature drop at the drierLiquid-line restriction
Low superheat, high subcooling, high head, clean condenserOvercharge
High suction, low head, low amps, small temperature splitCompressor not pumping