NATE HVAC Cheat Sheet: Key Facts
Every key takeaway and common trap from the NATE HVAC study guide on one page, grouped by chapter. Tap a lesson link to read the full explanation.
48 facts · 7 chaptersFacts checked 2026-11-15
Chapter 1
Safety
Key takeaways
- A locked disconnect is not proof of a dead circuit; test with a meter proved on a live source before and after. → Lockout, tagout and stored electrical energy
- Every worker on the equipment applies and removes only his or her own lock. → Lockout, tagout and stored electrical energy
- Never heat a refrigerant cylinder with a flame and never fill a recovery cylinder past its weight limit. → Refrigerant, cylinders and pressure hazards
- Suspected carbon monoxide exposure means people out and the appliance off before any diagnosis. → Carbon monoxide and combustion hazards
- A face shield goes over safety glasses, never in place of them. → PPE, brazing and job-site hazards
Common trap
- Wrong answers often offer a shortcut that sounds careful: working live with one hand in a pocket, using leather gloves as insulation, or letting a lead technician lock out for the whole crew. If the job can be done de-energized, the answer is to de-energize, lock out and verify. → Lockout, tagout and stored electrical energy
- Distractors treat a combustion defect as a comfort or efficiency issue: seal the crack with high-temperature sealant, raise the blower speed to dilute the leak, or leave the furnace running until the owner schedules a replacement. Any defect that can put flue gas into the living space means the appliance comes out of service now. → Carbon monoxide and combustion hazards
Quick reference
| Situation | Hazard | Safe practice |
|---|---|---|
| Charging cylinder transfers slowly | Flame spikes pressure and softens steel | Gentle warming such as a warm-water bath, within the marked limit |
| Filling a recovery cylinder | Liquid expands with heat and has no room | Fill by weight on a scale and keep a vapor space |
| Large leak in a basement | Vapor is heavier than air and displaces oxygen | Ventilate and test the air before entering |
Chapter 2
Tools & Measurement
Key takeaways
- An infrared thermometer reads the surface it sees, never the air, so air temperature needs a probe in the moving airstream. → Measuring temperature and proving the thermometer
- Heating air without adding moisture lowers relative humidity but leaves the dew point unchanged. → Humidity, wet bulb and dew point
- Absolute pressure equals gauge pressure plus local atmospheric pressure. → Gauge pressure, absolute pressure and vacuum
- Only a micron gauge and a decay test with the pump valved off prove a deep vacuum. → Gauge pressure, absolute pressure and vacuum
- Voltage is read in parallel on a live circuit, resistance on a dead and isolated component, and current with a clamp around one conductor. → Using electrical meters correctly
Common trap
- Wrong answers offer signs that feel convincing but prove nothing: cold hoses, a change in pump sound, or one low micron reading while the pump is still running. A vacuum is proven only by isolating the system and seeing the reading hold. → Gauge pressure, absolute pressure and vacuum
Quick reference
| Symptom | Cause | Fix |
|---|---|---|
| Coil reads lower ohms than expected | Parallel parts still wired in | Disconnect one lead to isolate it |
| Clamp on a whole cord reads near zero | Supply and return fields cancel | Clamp one conductor or use a line splitter |
| Odd readings on an ECM or inverter unit | Waveform is not a clean sine wave | Use a true-RMS meter |
Chapter 3
Basic Electrical
Key takeaways
- Ohm's law is E = I × R and the power formula is P = E × I; rearrange them to find the missing value. → Ohm's law, power and power factor
- Full source voltage across a switch that should be closed means that switch is open. → Series, parallel and reading a ladder diagram
- Loads are wired in parallel across the supply, while switches and safeties are wired in series with their own load. → Series, parallel and reading a ladder diagram
- Swapping any two line leads reverses a three-phase motor. → Transformers, single-phase and three-phase power
- On a compressor, the highest winding reading is start to run, and the terminal left out of it is common. → Single-phase motors, capacitors and winding tests
Common trap
- Distractors for these questions are usually the right digits in the wrong place: multiplying when you should divide, or moving the decimal point. Before choosing, check the size: a 240-volt heater drawing 12 amps cannot have 2,880 ohms of resistance. → Ohm's law, power and power factor
Quick reference
| Known readings | Formula | Result |
|---|---|---|
| 240 V across a heater, 12 A through it | R = E ÷ I | 20 ohms |
| 3,600 W element at 240 V | I = P ÷ E | 15 amps |
| Transformer rated 75 VA, 24 V secondary | I = VA ÷ V | About 3.1 amps |
Chapter 4
Science & Refrigeration Cycle
Key takeaways
- An air conditioner moves heat from indoors to outdoors; there is no such thing as cold energy. → Heat, sensible and latent heat, and heat transfer
- At saturation each pressure matches one temperature, which is what a pressure-temperature chart lists. → Saturation and the four main components
- Superheat is line temperature minus saturation temperature; subcooling is saturation temperature minus line temperature. → Calculating superheat and subcooling
- Fixed-orifice systems are charged by superheat and TXV systems by subcooling. → Metering devices and reading the charge
- High superheat with low subcooling points to an undercharge; high superheat with normal or high subcooling points to a restriction. → Metering devices and reading the charge
Common trap
- Expect distractors that add the two temperatures, call the saturation temperature itself the superheat, or swap the words superheat and subcooling. Superheat belongs to vapor on the suction side and subcooling belongs to liquid on the liquid line. → Calculating superheat and subcooling
- Distractors often reverse the metering logic: they claim a TXV closes down when the load rises, that a fixed orifice adjusts itself, or that TXV systems are charged by superheat. A TXV opens further on a rising load to hold its superheat, and that steady superheat is exactly why it cannot tell you the charge. → Metering devices and reading the charge
Quick reference
| Term | Meaning | HVAC example |
|---|---|---|
| Sensible heat | Changes temperature, no change of state | Lowering room dry-bulb temperature |
| Latent heat | Changes state, no temperature change | Condensing water vapor on the coil |
| Conduction | Heat moves by direct contact | A clamp-on probe on copper |
| Convection | A moving fluid carries heat | Air blown across a coil |
| Radiation | Energy travels as waves, no medium needed | An infrared thermometer reading a surface |
| Reading | Formula | Example |
|---|---|---|
| Superheat (suction line) | Line temperature minus saturation temperature | 55°F minus 45°F = 10°F |
| Subcooling (liquid line) | Saturation temperature minus line temperature | 105°F minus 95°F = 10°F |
Chapter 5
Construction, Comfort & Airflow
Key takeaways
- Insulation slows conducted heat, while air sealing stops air leakage; they are separate jobs. → The building envelope: insulation, air sealing and windows
- Size new equipment from a load calculation of the house as it is today, not from the old nameplate or square footage. → Loads, equipment sizing and comfort
- An oversized system short cycles and leaves the space cool but damp. → Loads, equipment sizing and comfort
- Higher static pressure on a fixed-speed blower means less airflow and less delivered capacity. → Airflow, static pressure and capacity
- Airflow from temperature rise is CFM = BTU/h ÷ (1.08 × ΔT). → Loads, equipment sizing and comfort
Common trap
- Wrong answers treat insulation as the fix for everything: pile more batts over an open hatch, or fill the cavity so condensation cannot happen. More insulation does not stop air leaks, and moist air still condenses on any surface below its dew point. → The building envelope: insulation, air sealing and windows
- A common wrong answer says a restriction makes the blower work harder and move more air, or that higher static pressure only shows the blower is doing its job. On a fixed-speed blower, more resistance always means less air and less delivered capacity. → Airflow, static pressure and capacity
- Watch for answers that fix one symptom by hurting the whole system: slowing the blower for the whole house to quiet one register, or choking a balancing damper until the noise stops. Fix the branch, the filter area or the leak where the problem actually is. → Duct leakage, noise, filters and ventilation
Chapter 6
AC Components & Operation
Key takeaways
- Compressors pump vapor; liquid reaching them breaks parts and washes away oil, so crankcase heaters and accumulators keep it out. → Compressors and keeping liquid out
- Warmer outdoor air or a dirty condenser raises condensing temperature and head pressure. → Outdoor coil, indoor coil and condensate
- Low airflow across the indoor coil drops coil temperature until the coil can freeze. → Outdoor coil, indoor coil and condensate
- A TXV bulb goes tight on top of a small horizontal suction line, or at 4 or 8 o'clock on lines 7/8 inch and larger, and is insulated. → Metering devices, the TXV bulb and charging method
- Service valves run back seated; front seating isolates the compressor. → Line sets, accessories, service valves and thermostats
Common trap
- Do not mix up the accumulator and the receiver. The accumulator is on the low side and protects the compressor from liquid; the receiver is on the high side and stores liquid. Neither one filters acid or moisture; that is the filter-drier's job. → Compressors and keeping liquid out
- Distractors often claim a condensate trap stops refrigerant from escaping, or that a float switch only sounds an alarm or bypasses water to keep the system running. The trap blocks air drawn in by negative pressure, and the float switch opens the control circuit so the system stops making water. → Outdoor coil, indoor coil and condensate
Quick reference
| Part | Where | Job |
|---|---|---|
| Crankcase heater | On the compressor | Keeps oil warm during the off cycle so refrigerant does not migrate into it |
| Accumulator | Suction line, low side | Traps liquid leaving the evaporator and meters oil back through a small hole |
| Receiver | Liquid line, high side | Stores surplus liquid for a variable charge |
Chapter 7
AC Diagnosis & Service
Key takeaways
- Read superheat and subcooling together; each fault has its own combination. → Reading superheat and subcooling patterns
- Non-condensables make both head pressure and subcooling read high, which looks like an overcharge. → Reading superheat and subcooling patterns
- In a control string, the device with full source voltage across it is the open one. → Troubleshooting the control circuit
- Prove the cheap part before condemning the expensive one, such as the run capacitor before the compressor. → Reading superheat and subcooling patterns
- Find where high static pressure is by measuring the drop across each component. → Airside, static pressure and condensate problems
Common trap
- Expect an answer that simply adds refrigerant whenever suction pressure is low. Low suction comes from undercharge, restriction and low airflow alike, and adding refrigerant to a restricted or airflow-starved system overcharges it. Even a true undercharge calls for finding and repairing the leak first. → Reading superheat and subcooling patterns
- Never pick an answer that jumpers, bypasses or resets a safety without fixing the cause, or that installs larger fuses to keep a unit on line. Safety controls and overcurrent devices report real faults; removing them only removes the protection. → Troubleshooting the control circuit
Quick reference
| Pattern | Likely fault |
|---|---|
| High superheat, low subcooling, low pressures | Undercharge from a leak; find and fix the leak |
| High superheat, high subcooling, temperature drop at the drier | Liquid-line restriction |
| Low superheat, high subcooling, high head, clean condenser | Overcharge |
| High suction, low head, low amps, small temperature split | Compressor not pumping |