Quibank app: now on the App Store — free, works offline. Get the app ↗

Chapters0/29 ▾
  1. 1.Safety0/4
    1. Lockout, tagout and stored electrical energy
    2. Refrigerant, cylinders and pressure hazards
    3. Carbon monoxide and combustion hazards
    4. PPE, brazing and job-site hazards
  2. 2.Tools & Measurement0/5
    1. Measuring temperature and proving the thermometer
    2. Humidity, wet bulb and dew point
    3. Gauge pressure, absolute pressure and vacuum
    4. Using electrical meters correctly
    5. Airflow, leak detection and charging tools
  3. 3.Basic Electrical0/4
    1. Ohm's law, power and power factor
    2. Series, parallel and reading a ladder diagram
    3. Transformers, single-phase and three-phase power
    4. Single-phase motors, capacitors and winding tests
  4. 4.Science & Refrigeration Cycle0/4
    1. Heat, sensible and latent heat, and heat transfer
    2. Saturation and the four main components
    3. Calculating superheat and subcooling
    4. Metering devices and reading the charge
  5. 5.Construction, Comfort & Airflow0/4
    1. The building envelope: insulation, air sealing and windows
    2. Loads, equipment sizing and comfort
    3. Airflow, static pressure and capacity
    4. Duct leakage, noise, filters and ventilation
  6. 6.AC Components & Operation0/4
    1. Compressors and keeping liquid out
    2. Outdoor coil, indoor coil and condensate
    3. Metering devices, the TXV bulb and charging method
    4. Line sets, accessories, service valves and thermostats
  7. 7.AC Diagnosis & Service0/4
    1. Reading superheat and subcooling patterns
    2. Troubleshooting the control circuit
    3. Compressor electrical faults
    4. Airside, static pressure and condensate problems
Saved in this browser. Move it to another device →
← AC Components & Operation

Chapter 6 · Lesson 4 of 4

Line sets, accessories, service valves and thermostats

1 min read

Oil leaves the compressor with the refrigerant and comes back only if the suction vapor moves fast enough to carry it, which is hardest up a tall vertical riser.

A suction line that is too large drops velocity and strands oil; one that is too small adds friction loss and costs capacity, so line sizes come from the manufacturer's data for the actual length and lift.

Suction-line insulation keeps the cold line from picking up heat that never reaches the house; crushed or soaked insulation also sweats and drips, so it is replaced.

  • The liquid-line filter-drier traps moisture, acid and dirt ahead of the metering device, with its arrow pointing in the direction of flow.
  • Back seated is the running position; mid-seated lets gauges read while the system runs; front seated isolates the compressor.
  • A thermostat belongs on an interior wall, away from sun, supply air, doors and appliances, so it senses the real room.
  • Deep evacuation lowers pressure until water boils off and removes air, which would otherwise raise head pressure.

Example: a basement air handler feeds a rooftop condenser through a long vertical suction riser, and the installer used a larger suction line than the chart called for to cut pressure drop.

Vapor velocity in the riser falls, oil stays in the line, and the compressor runs short of oil. Line sizing follows the manufacturer's data, not the idea that bigger is always better.

Check yourself

1. A compressor service valve has been turned fully in onto its front seat. What has that accomplished, and what is the valve's normal operating position?

2. A long line set on a split system includes a tall vertical suction riser from a basement air handler up to a rooftop condensing unit. Why is suction-line size critical on this installation?