Chapters0/29 ▾
Chapter 2 · Lesson 1 of 5
Measuring temperature and proving the thermometer
1 min read
Electronic temperature sensors work in two main ways. A thermocouple is a junction of two different metals that produces a small millivolt signal, which gives it a very wide range.
A thermistor is a semiconductor whose resistance changes sharply with temperature, which makes it very sensitive over a narrower range. An infrared thermometer is different again: it reads the infrared energy radiated by a surface, and air is nearly transparent to that energy.
- Aimed through a supply register, an infrared thermometer reads the vanes and duct, not the supply air.
- A probe touching the duct wall or facing the coil reads metal and radiant heat. Put the tip in the moving air and wait until the display stops changing.
- A stirred bath of crushed ice and water is a reliable fixed point. Boiling water works only if you account for elevation.
Example: two thermometers in the same return air disagree by 4°F. Averaging them, or trusting the one with more decimal places, is wrong. Check both in an ice bath and use the one that reads the fixed point correctly. Then adjust, repair or retire the other one.
Check yourself
1. A technician points an infrared thermometer through the face of a supply register to obtain the supply-air temperature. What is the instrument actually measuring?
2. Which statement correctly describes the difference between a thermocouple and a thermistor used as temperature sensors?
Facts checked 2026-11-15 · Sources: NATE: Certification exams
NATE HVAC cheat sheet: every key fact on one page →