Metering devices and reading the charge
1 min read
A thermostatic expansion valve senses the refrigerant leaving the coil and opens or closes to hold superheat near a set value as the load changes.
An electronic expansion valve does the same job, but a controller positions it from electronic temperature and pressure sensors, so it can hold superheat more tightly. A fixed orifice or capillary tube has one fixed passage, so its superheat swings with load and charge.
That difference decides the charging method. On a fixed-orifice system, superheat moves directly with charge, so it is compared with the manufacturer's chart for the measured outdoor dry bulb and indoor wet bulb.
On a TXV system, superheat stays fairly steady, so subcooling is the meaningful check. Blends are charged as liquid, metered so the compressor does not get a slug, because drawing vapor changes the blend's makeup.
Example: a system shows low suction pressure and high superheat, with good airflow and a clean coil. If subcooling is low, there is too little refrigerant. If subcooling is normal or high and the liquid line is colder just past the filter-drier, liquid is dammed behind a restriction.