Quibank app: now on the App Store — free, works offline. Get the app ↗

Chapters0/29 ▾
  1. 1.Safety0/4
    1. Lockout, tagout and stored electrical energy
    2. Refrigerant, cylinders and pressure hazards
    3. Carbon monoxide and combustion hazards
    4. PPE, brazing and job-site hazards
  2. 2.Tools & Measurement0/5
    1. Measuring temperature and proving the thermometer
    2. Humidity, wet bulb and dew point
    3. Gauge pressure, absolute pressure and vacuum
    4. Using electrical meters correctly
    5. Airflow, leak detection and charging tools
  3. 3.Basic Electrical0/4
    1. Ohm's law, power and power factor
    2. Series, parallel and reading a ladder diagram
    3. Transformers, single-phase and three-phase power
    4. Single-phase motors, capacitors and winding tests
  4. 4.Science & Refrigeration Cycle0/4
    1. Heat, sensible and latent heat, and heat transfer
    2. Saturation and the four main components
    3. Calculating superheat and subcooling
    4. Metering devices and reading the charge
  5. 5.Construction, Comfort & Airflow0/4
    1. The building envelope: insulation, air sealing and windows
    2. Loads, equipment sizing and comfort
    3. Airflow, static pressure and capacity
    4. Duct leakage, noise, filters and ventilation
  6. 6.AC Components & Operation0/4
    1. Compressors and keeping liquid out
    2. Outdoor coil, indoor coil and condensate
    3. Metering devices, the TXV bulb and charging method
    4. Line sets, accessories, service valves and thermostats
  7. 7.AC Diagnosis & Service0/4
    1. Reading superheat and subcooling patterns
    2. Troubleshooting the control circuit
    3. Compressor electrical faults
    4. Airside, static pressure and condensate problems
Saved in this browser. Move it to another device →
← AC Components & Operation

Chapter 6 · Lesson 3 of 4

Metering devices, the TXV bulb and charging method

1 min read

A thermostatic expansion valve balances bulb pressure, which pushes it open, against evaporator pressure plus spring force, which push it closed. Because it feeds the coil to hold its superheat setting, superheat stays nearly the same whether the system is a little low or a little full.

Charge shows up instead as liquid backed up in the condenser, so a TXV system is charged by subcooling to the manufacturer's value. A fixed orifice or capillary tube has no feedback, so superheat moves with charge and load, and it is read against the manufacturer's target-superheat table.

  • Mount the bulb with tight metal-to-metal contact on top of a horizontal suction line. On lines 7/8 inch and larger, valve makers call for the 4 or 8 o'clock position. Never mount it on the bottom, where oil runs.
  • Insulate the bulb so it reads the refrigerant, not the surrounding air.
  • A coil fed through a distributor needs an external equalizer, tapped into the suction line downstream of the bulb, so the valve sees true coil-outlet pressure.

Example: a bulb strapped loosely to the bottom of the suction line reads oil and air instead of vapor, so the valve hunts or floods the coil. Moving it to the correct position and insulating it fixes the feed.

Check yourself

1. Where and how should the sensing bulb of a thermostatic expansion valve be mounted on the suction line?

2. A split system uses a thermostatic expansion valve at the indoor coil. Which refrigerant-side measurement is the meaningful check of charge on that system, and why?