Quibank app: now on the App Store — free, works offline. Get the app ↗

Chapters0/29 ▾
  1. 1.Safety0/4
    1. Lockout, tagout and stored electrical energy
    2. Refrigerant, cylinders and pressure hazards
    3. Carbon monoxide and combustion hazards
    4. PPE, brazing and job-site hazards
  2. 2.Tools & Measurement0/5
    1. Measuring temperature and proving the thermometer
    2. Humidity, wet bulb and dew point
    3. Gauge pressure, absolute pressure and vacuum
    4. Using electrical meters correctly
    5. Airflow, leak detection and charging tools
  3. 3.Basic Electrical0/4
    1. Ohm's law, power and power factor
    2. Series, parallel and reading a ladder diagram
    3. Transformers, single-phase and three-phase power
    4. Single-phase motors, capacitors and winding tests
  4. 4.Science & Refrigeration Cycle0/4
    1. Heat, sensible and latent heat, and heat transfer
    2. Saturation and the four main components
    3. Calculating superheat and subcooling
    4. Metering devices and reading the charge
  5. 5.Construction, Comfort & Airflow0/4
    1. The building envelope: insulation, air sealing and windows
    2. Loads, equipment sizing and comfort
    3. Airflow, static pressure and capacity
    4. Duct leakage, noise, filters and ventilation
  6. 6.AC Components & Operation0/4
    1. Compressors and keeping liquid out
    2. Outdoor coil, indoor coil and condensate
    3. Metering devices, the TXV bulb and charging method
    4. Line sets, accessories, service valves and thermostats
  7. 7.AC Diagnosis & Service0/4
    1. Reading superheat and subcooling patterns
    2. Troubleshooting the control circuit
    3. Compressor electrical faults
    4. Airside, static pressure and condensate problems
Saved in this browser. Move it to another device →
← Tools & Measurement

Chapter 2 · Lesson 2 of 5

Humidity, wet bulb and dew point

1 min read

A sling psychrometer has a dry-bulb thermometer and a wet-bulb thermometer covered by a wet wick. Water evaporating from the wick cools the wet bulb, and the drier the air, the faster it evaporates.

The difference between the two readings, called the wet-bulb depression, therefore grows as relative humidity falls. The wet bulb can never read higher than the dry bulb, and when the two match, the air is saturated at 100 percent relative humidity.

  • Wet the wick with distilled water, since minerals in tap water slow evaporation.
  • Whirl it away from your body and out of direct sun until the wet bulb stops falling, then read the wet bulb first.

Dew point describes how much moisture is actually in the air. Relative humidity compares that moisture with the most the air could hold at its current temperature.

Example: a psychrometer reads 78°F dry bulb and 64°F wet bulb, a depression of 14°F, which works out to about 46 percent relative humidity. If a furnace then heats that air without adding water, the dew point stays the same while relative humidity drops, because warmer air could hold more.

Check yourself

1. A furnace heats a stream of air without adding any moisture to it. What happens to the relative humidity and to the dew point of that air?

2. In one space a psychrometer shows the dry-bulb reading well above the wet-bulb reading; in a second space the two readings are nearly identical. What does this tell the technician about the air in each space?