Chapter 3 · Lesson 2 of 4
Series, parallel and reading a ladder diagram
1 min read
In a series circuit the same current flows through every device, so one open device stops the whole string. That is why safety controls such as limits, rollout switches and pressure switches are wired in series with the load they protect, and why an open safety often shows up as a dead unit with no fault message.
In a parallel circuit every branch sees the same voltage and the branch currents add. If one of two parallel fan motors opens, the other keeps running at full voltage and only the total current drops.
- On a ladder diagram, the two side rails are the power source, L1 and L2 or the hot and common of the control transformer.
- Each rung is one circuit with one load at the right, and the switches that control it in series to its left.
- A relay or contactor links two circuits: a small control circuit energizes the coil, and its contacts switch the larger load circuit.
- An electric heat sequencer uses a small heater and a bimetal to close its contacts after a delay, bringing elements on in stages.
Example: with a call for cooling and 24 volts available, you read 0 volts across the thermostat contacts and 24 volts across a pressure switch. A closed contact drops almost no voltage, so the pressure switch is the open device.