Troubleshooting the control circuit

1 min read

Low-voltage controls are wired in series, so you can walk the string with a voltmeter. A closed switch reads near 0 volts across it. An open switch reads the full source voltage, because the meter completes the path through the load.

Example: with 24 volts at the transformer, 0 volts across the thermostat contacts, 24 volts across the high-pressure switch and 0 volts at the contactor coil, the high-pressure switch is open. The next job is finding out why it opened, such as a dirty condenser, a failed fan, an overcharge or air in the system.

  • A contactor that chatters usually has coil voltage sagging under load. Measure coil voltage while it tries to pull in, not at rest.
  • If the compressor keeps running with the coil wire removed, the contacts are welded. Open the disconnect, lock it out and replace the contactor.
  • A manual-reset high-pressure control that has tripped is reporting a problem. Correct the cause, then reset and verify pressures.

Check yourself

1. On a no-cooling call the thermostat is calling, control voltage is present at the transformer secondary, 0 V is measured across the closed thermostat contacts, source voltage is measured across the two terminals of a pressure switch in the control string, and 0 V is measured across the contactor coil. What does this tell the technician?

2. A technician arrives to find a system locked out on a manual-reset high-pressure control. The customer is uncomfortable and asks to have the unit running before the technician leaves. What is the correct procedure?