Chapters0/29 ▾
Chapter 7 · Lesson 1 of 4
Reading superheat and subcooling patterns
1 min read
Superheat tells you how well the evaporator is fed, and subcooling tells you how much liquid is stacked in the condenser. Reading them together, after airflow and coil condition are verified, points to the fault. A single pressure reading cannot do that, because several different faults all pull suction pressure down.
| Pattern | Likely fault |
|---|---|
| High superheat, low subcooling, low pressures | Undercharge from a leak; find and fix the leak |
| High superheat, high subcooling, temperature drop at the drier | Liquid-line restriction |
| Low superheat, high subcooling, high head, clean condenser | Overcharge |
| High suction, low head, low amps, small temperature split | Compressor not pumping |
High head pressure with high subcooling has more than one cause. Before removing refrigerant, prove the condenser can reject heat: a dirty coil, a slow fan or recirculating air gives the same picture as an overcharge.
Non-condensables, usually air left by a poor evacuation, also make both head pressure and subcooling read high, with a condensing saturation temperature far above outdoor air. The fix is to recover, evacuate to a deep vacuum checked with a micron gauge, and recharge by weight.
Example: after thawing an iced coil, low subcooling points to low charge, while normal or high subcooling with low superheat points to low airflow.
Check yourself
1. On a cooling call the technician measures 25°F superheat and 18°F subcooling. Suction pressure is low, head pressure is normal to slightly high, and the liquid line is noticeably cooler and lightly sweating immediately downstream of the filter-drier. What does this combination indicate?
2. Following a compressor change-out done in a hurry, a system runs with head pressure far higher than the outdoor ambient would produce, subcooling reading higher than normal, and a condensing saturation temperature far above the outdoor air temperature. The condenser is clean and the charge was weighed in. What is the most likely cause?
Facts checked 2026-11-15 · Sources: NATE: Certification exams
NATE HVAC cheat sheet: every key fact on one page →