Quibank app: now on the App Store — free, works offline. Get the app ↗

Chapters0/29 ▾
  1. 1.Safety0/4
    1. Lockout, tagout and stored electrical energy
    2. Refrigerant, cylinders and pressure hazards
    3. Carbon monoxide and combustion hazards
    4. PPE, brazing and job-site hazards
  2. 2.Tools & Measurement0/5
    1. Measuring temperature and proving the thermometer
    2. Humidity, wet bulb and dew point
    3. Gauge pressure, absolute pressure and vacuum
    4. Using electrical meters correctly
    5. Airflow, leak detection and charging tools
  3. 3.Basic Electrical0/4
    1. Ohm's law, power and power factor
    2. Series, parallel and reading a ladder diagram
    3. Transformers, single-phase and three-phase power
    4. Single-phase motors, capacitors and winding tests
  4. 4.Science & Refrigeration Cycle0/4
    1. Heat, sensible and latent heat, and heat transfer
    2. Saturation and the four main components
    3. Calculating superheat and subcooling
    4. Metering devices and reading the charge
  5. 5.Construction, Comfort & Airflow0/4
    1. The building envelope: insulation, air sealing and windows
    2. Loads, equipment sizing and comfort
    3. Airflow, static pressure and capacity
    4. Duct leakage, noise, filters and ventilation
  6. 6.AC Components & Operation0/4
    1. Compressors and keeping liquid out
    2. Outdoor coil, indoor coil and condensate
    3. Metering devices, the TXV bulb and charging method
    4. Line sets, accessories, service valves and thermostats
  7. 7.AC Diagnosis & Service0/4
    1. Reading superheat and subcooling patterns
    2. Troubleshooting the control circuit
    3. Compressor electrical faults
    4. Airside, static pressure and condensate problems
Saved in this browser. Move it to another device →
← AC Diagnosis & Service

Chapter 7 · Lesson 1 of 4

Reading superheat and subcooling patterns

1 min read

Superheat tells you how well the evaporator is fed, and subcooling tells you how much liquid is stacked in the condenser. Reading them together, after airflow and coil condition are verified, points to the fault. A single pressure reading cannot do that, because several different faults all pull suction pressure down.

PatternLikely fault
High superheat, low subcooling, low pressuresUndercharge from a leak; find and fix the leak
High superheat, high subcooling, temperature drop at the drierLiquid-line restriction
Low superheat, high subcooling, high head, clean condenserOvercharge
High suction, low head, low amps, small temperature splitCompressor not pumping

High head pressure with high subcooling has more than one cause. Before removing refrigerant, prove the condenser can reject heat: a dirty coil, a slow fan or recirculating air gives the same picture as an overcharge.

Non-condensables, usually air left by a poor evacuation, also make both head pressure and subcooling read high, with a condensing saturation temperature far above outdoor air. The fix is to recover, evacuate to a deep vacuum checked with a micron gauge, and recharge by weight.

Example: after thawing an iced coil, low subcooling points to low charge, while normal or high subcooling with low superheat points to low airflow.

Check yourself

1. On a cooling call the technician measures 25°F superheat and 18°F subcooling. Suction pressure is low, head pressure is normal to slightly high, and the liquid line is noticeably cooler and lightly sweating immediately downstream of the filter-drier. What does this combination indicate?

2. Following a compressor change-out done in a hurry, a system runs with head pressure far higher than the outdoor ambient would produce, subcooling reading higher than normal, and a condensing saturation temperature far above the outdoor air temperature. The condenser is clean and the charge was weighed in. What is the most likely cause?

Facts checked 2026-11-15 · Sources: NATE: Certification exams

NATE HVAC cheat sheet: every key fact on one page →