Chapter 7 · Lesson 3 of 4
Compressor electrical faults
1 min read
A compressor that hums for a few seconds and trips its internal overload, with correct voltage at the contactor, is drawing locked-rotor current. On a permanent split capacitor compressor, a failed run capacitor causes exactly that, so test the capacitor first, with power off and the capacitor discharged.
Winding tests are done with power off and leads removed. In a healthy single-phase compressor, common to run is lowest, common to start is higher, and run to start equals their sum.
- Continuity from a terminal to the shell means a grounded winding: replace the compressor and clean up the burnout with new driers and an acid test.
- Infinite readings on both paths that include the start terminal mean an open start winding, which cannot be repaired in the field.
- Arced, discolored terminals with oil around them are a terminal-venting hazard. Keep the unit locked out; never re-energize it to watch.
- A three-phase scroll that is loud, low on amps and builds almost no pressure difference is running backward. Swap any two supply legs quickly.
Example: with power off and leads removed, a technician reads 2 ohms common to run, 4 ohms common to start and 6 ohms run to start, but 0 ohms from the common terminal to the shell.
The winding readings add up correctly, yet the path to the shell shows a ground. The compressor is replaced, and the system is cleaned up afterward.
Check yourself
1. The outdoor fan runs normally, but the compressor hums for a few seconds and then trips on its internal overload. Line voltage measured at the load side of the contactor while the compressor attempts to start is within the nameplate range. What is the most appropriate next step?
2. With the power off and the compressor leads removed, a technician measures common-to-run at 1.9 ohms, common-to-start as infinite (no continuity), and run-to-start as infinite. No terminal reads continuity to the shell. What do these readings indicate?