Chapters0/32 ▾
Chapter 3 · Lesson 4 of 5
The refrigeration cycle, superheat and EPA Section 608
1 min read
Refrigerant travels through the compressor, the condenser, the metering device and the evaporator. The compressor discharges hot, high-pressure vapor. The condenser outdoors rejects that heat and turns it into a high-pressure liquid, which travels in the liquid line to the metering device.
After the metering device the pressure drops, and the evaporator boils the low-pressure liquid into the low-pressure vapor that returns to the compressor.
Superheat is how far the suction vapor has warmed above the temperature at which the refrigerant boiled. Subcooling is how far the liquid leaving the condenser has cooled below the temperature at which it condensed.
Example: a contractor reads a 38°F boiling temperature and a 49°F suction line, so superheat is 49 − 38 = 11°F. A 105°F condensing temperature and a 96°F liquid line give 105 − 96 = 9°F of subcooling.
- EPA counts anyone who attaches gauges to measure pressure as a technician, so an uncertified technician does not connect them.
- Refrigerant in scrapped window units must be recovered before disposal; venting is prohibited indoors or out.
- An old thermostat with a mercury bulb is kept intact and sent for universal waste recycling.
Check yourself
1. An HVAC contractor's readings on an apartment air conditioner show an evaporator saturation (boiling) temperature of 40°F and a suction line temperature of 52°F at the outdoor unit. How should the result be described?
2. A contractor explains that a system's refrigerant charge was checked by measuring subcooling at the liquid line. What does subcooling describe?
Facts checked 2026-11-15 · Sources: NAAEI: Certificate for Apartment Maintenance Technicians (CAMT), EPA: Section 608 of the Clean Air Act (refrigerant management), EPA: Universal waste (mercury-containing equipment)
CAMT Apartment Maintenance cheat sheet: every key fact on one page →