Boilers, heat pumps and air conditioning
1 min read
A hot-water boiler needs an air cushion to absorb expansion because water barely compresses. When an old steel expansion tank waterlogs, the whole tank feels equally hot, pressure spikes each cycle and the relief valve drips.
The valve is the symptom, not the defect. A heat pump in winter delivers a large volume of air near or below skin temperature, so it feels cool while heating normally, and its defrost cycle briefly stops the outdoor fan and releases a plume of vapor. Both are normal.
Do not run air conditioning after a cold spell: refrigerant migrates into the compressor and the oil thickens, so starting it risks damage. Report that it was not operated and why. When it is warm enough, the temperature split is a screening check.
Example: return air 76 °F and supply air 58 °F after the system stabilizes gives an 18-degree split, which is compared with the range the manufacturer expects.
A split outside that range, an iced evaporator with frost on the suction line, or water dripping from a secondary drain above a window are all reported for evaluation. That secondary drain is a warning that the primary condensate drain is blocked.
Check yourself
1. An inspector wants a simple screening check of whether an operating central air conditioner is cooling as it should. Which description of the temperature-split method is correct?
2. A hot water boiler's pressure-temperature relief valve drips every time the system heats up, the pressure gauge climbs well above its cold reading during each firing cycle, and the steel expansion tank above the boiler feels equally hot along its entire length. Which explanation is most consistent with these observations?
Facts checked 2026-11-15 · Sources: National Home Inspector Examination (EBPHI), InterNACHI Home Inspection Standards of Practice
Home Inspector Practice Test (NHIE) cheat sheet: every key fact on one page →