Quibank app: now on the App Store — free, works offline. Get the app ↗

Chapters0/29 ▾
  1. 1.Structure & Foundation0/5
    1. Footings, soil movement and foundation crack patterns
    2. Water below grade and in crawl spaces
    3. Load path, columns and floor framing
    4. Roof framing: rafters, ridges and trusses
    5. Decay and wood-destroying organisms
  2. 2.Roofing, Exterior & Site0/5
    1. Roof coverings: how they keep water out and how they fail
    2. Flashings and roof penetrations
    3. Roof drainage, ice dams and chimney tops
    4. Walls, cladding and windows as drained assemblies
    5. Decks, grading and retaining walls
  3. 3.Electrical Systems0/5
    1. Service entrance and capacity
    2. Grounding, bonding and the neutral
    3. Inside the panel: overcurrent protection and terminations
    4. Ground-fault, arc-fault and receptacle testing
    5. Older wiring, workmanship defects and generators
  4. 4.Plumbing Systems0/4
    1. Water supply and piping materials
    2. Traps, vents and drain defects
    3. Water heaters, relief valves and gas connections
    4. Cross-connections, backflow and fixture leaks
  5. 5.HVAC, Insulation & Ventilation0/5
    1. Furnace combustion safety
    2. Venting, draft and house depressurization
    3. Boilers, heat pumps and air conditioning
    4. Insulation, air barriers and vapor retarders
    5. Attic ventilation, crawl spaces and exhaust ducts
  6. 6.Standards, Ethics & Reporting0/5
    1. What a home inspection is and is not
    2. Material defects and how to classify findings
    3. Writing the report: methods, limits and wording
    4. Exclusions, environmental hazards and immediate dangers
    5. Agreements, confidentiality and conflicts of interest
Saved in this browser. Move it to another device →
← Electrical Systems

Chapter 3 · Lesson 2 of 5

Grounding, bonding and the neutral

1 min read

ConductorNormal job
Grounded conductor (neutral)Carries return current all the time as part of the circuit
Equipment grounding conductorIdle by design; during a fault it gives a low-impedance path so the breaker trips fast

The two are joined at one point only, the service disconnecting means. In a subpanel, such as one feeding a detached garage, the neutral bar must be isolated from the enclosure and the grounds kept on a separate bar.

If the factory bonding screw is left in and neutrals and grounds share bars, return current splits between the neutral feeder and every parallel metal path, including the grounding conductor, conduit, cable armor and bonded piping. Normally dead metal then carries working current and can rise above ground potential.

Metal water and gas piping are bonded to the electrical system to hold them at the same potential as other grounded metal and to give fault current a path back to the source, so a pipe touched by a live conductor trips the breaker instead of staying energized.

Bonding is about equal potential and fault clearing, not corrosion protection or static.

Grounding to earth through electrodes is a separate idea from bonding. If an answer says bonding exists to slow corrosion, drain static, or let the piping replace the grounding electrode, it describes something bonding does not do.

Check yourself

1. In a subpanel serving a detached garage, the inspector sees the neutral bar bonded to the enclosure by a factory bonding screw and the grounded conductors and equipment grounding conductors landed together on the same bars. What is the specific failure this creates?

2. A client asks the inspector to explain the difference between the grounded conductor and the equipment grounding conductor in the branch circuits of the house. Which explanation is correct?