Ground-fault, arc-fault and receptacle testing
1 min read
A ground-fault circuit interrupter compares current going out on the hot conductor with current coming back on the neutral and opens on a very small imbalance, a people-protection threshold far below any breaker trip.
An arc-fault device instead watches the waveform for the erratic signature of arcing at damaged cable or loose terminals, a fire condition that creates no imbalance at all. They see different events, so arc-fault protection in bedrooms does not replace ground-fault protection in a bathroom.
Because it only compares the two circuit conductors, a ground-fault receptacle works on an old two-wire circuit with no equipment ground. It does not create a ground for whatever is plugged in, so it must be labeled to disclose that. On such circuits the acceptable fixes are a real equipment ground, a non-grounding receptacle, or ground-fault protection with labels.
A three-light tester that reads correct on an ungrounded circuit may be fooled by a bootleg jumper from neutral to ground, which ties appliance cases to a current-carrying conductor. Reversed polarity at a lampholder energizes the screw shell, the part people touch when changing a bulb.
Check yourself
1. A three-slot receptacle in an older house reads "correct" on a three-light plug-in tester, but the inspector suspects the branch circuit has no equipment grounding conductor. What does this combination most likely indicate, and why does it matter?
2. A client asks whether the arc-fault protection in the bedrooms makes the ground-fault protection in the bathroom unnecessary. What is the correct explanation of the two protective functions?