Hydrants, water pressure and drafting
Varies by state. Your state sets this exam: the number of questions, time limit, pass mark and any state-law section can differ from this practice. Check your state's official handbook or licensing board before you test.
1 min read
Exam questions about water supply start with three pressure words. Static pressure is the reading in the main when no water is moving. Residual pressure is what is left in the system while water flows.
Velocity, or pitot, pressure is the forward push of a stream measured with a pitot gauge at an open outlet. Elevation pressure has to do with height, not flow. For example, if a capped hydrant reads 80 psi at rest and 62 psi while a neighboring hydrant flows, 80 is static and 62 is residual.
While pumping from a hydrant, the operator stops adding flow when the intake residual falls toward about 20 psi. Going lower can damage the main, draw contaminants back into drinking water and starve other users.
Dry-barrel hydrants, used where winters freeze, are opened fully and slowly: the drain stays open whenever the main valve is only partly open, so a half-open hydrant pushes water out the drain and washes away the soil around it. When there is no hydrant, an engine drafts from a pond or tank through hard suction hose, which stays rigid under vacuum; soft sleeve hose would collapse.
| Bonnet color (NFPA) | Class | Rated flow |
|---|---|---|
| Light blue | AA | 1,500 gpm or more |
| Green | A | 1,000 to 1,499 gpm |
| Orange | B | 500 to 999 gpm |
| Red | C | Under 500 gpm |
Check yourself
1. During a hydrant flow test, a cap gauge on the test hydrant reads 72 psi with no water moving and 58 psi while a nearby hydrant flows. What does the 58 psi reading represent?
2. An engine is pumping from a hydrant, and the operator watches the intake gauge fall as more lines are opened. Below about what residual pressure should the operator stop increasing flow to protect the water system?