Foam, flammable liquids and BLEVE prevention
Varies by state. Your state sets this exam: the number of questions, time limit, pass mark and any state-law section can differ from this practice. Check your state's official handbook or licensing board before you test.
1 min read
Know three foam words. Concentrate is the liquid in the container. Foam solution is concentrate plus water. Finished foam is solution with air added. A 3% concentrate means 3 parts concentrate to 97 parts water in the solution.
Example: to make 200 gallons of solution with a 6% concentrate, you need 0.06 x 200 = 12 gallons of concentrate and 188 gallons of water. How much the foam grows is a separate number, the expansion ratio.
- Polar solvents such as ethanol mix with water and destroy ordinary foam, so they need alcohol-resistant concentrate.
- Bank-down bounces foam off a wall or object next to the fuel; roll-on bounces it off open ground ahead of the spill; rain-down lofts it overhead and is least preferred. Never plunge foam into the fuel.
- An in-line eductor picks up concentrate only when the nozzle flow matches its rating, such as a 95 gpm eductor with a 95 gpm nozzle.
For flame impinging on an LPG tank, aim cooling streams at the upper shell above the liquid level. Below that level the boiling liquid carries heat away from the steel, but the metal around the vapor space has no such protection, weakens and can fail in a BLEVE.
Check yourself
1. A tanker carrying ethanol has overturned, and the spilled fuel is burning. Which foam concentrate is needed?
2. Flame is impinging on a horizontal LPG tank. Where should cooling streams be concentrated to reduce the risk of a BLEVE?
Facts checked 2026-11-15 · Sources: NFPA 1010 (2024): Professional Qualifications for Firefighters, FEMA: National Incident Management System (NIMS) doctrine, NFPA 11: Low-, Medium-, and High-Expansion Foam
Firefighter I & II Certification cheat sheet: every key fact on one page →