Quibank app: now on the App Store — free, works offline. Get the app ↗

33 Structure & Foundation Practice Questions & Answers

Every Structure & Foundation practice question from the Home Inspector Practice Test (NHIE), with the correct answer and a short explanation.

Start practice test →
  1. 1. An inspector is explaining to a client why a residential foundation wall is built on a footing that is wider than the wall itself. What is the footing's primary structural function?

    • A.To form a waterproof barrier beneath the wall so that groundwater in the surrounding soil is blocked before it can reach the basement floor
    • B.To spread the load from the wall over a larger area of soil so that the bearing pressure stays within what the soil can carry✓ Answer
    • C.To resist the inward lateral pressure that backfill soil exerts against the wall, transferring that horizontal thrust into the ground beside the footing
    • D.To act as a capillary break wider than the wall itself so that moisture in the soil cannot rise through the masonry into the framing above

    A footing works by distributing a concentrated wall load across enough soil area that the resulting bearing pressure remains below the soil's allowable bearing capacity, which is why footings must sit on undisturbed native soil or engineered fill rather than on loose backfill or organic topsoil. Waterproofing, resisting lateral soil pressure, and capillary breaks are performed by other components of the assembly.

    Ref QB-HNH9UDSource: National Home Inspector Examination content outline — structural systems: foundations and footingsReport a problem with this question

  2. 2. In a basement with concrete block foundation walls, an inspector observes a continuous horizontal crack along a mortar joint near mid-height of one wall, with the courses above the crack displaced inward relative to the courses below. What does this pattern most strongly indicate?

    • A.Frost heave beneath the footing, which lifts the lower courses each winter and shears the wall along a bed joint
    • B.Lateral pressure from the backfill soil, frequently made worse by water saturating the soil behind the wall✓ Answer
    • C.Settlement of the footing beneath that wall, which lets the lower courses drop and splits the wall along a bed joint
    • D.Normal shrinkage of the mortar as the wall cured, which commonly opens one long bed joint in a block wall

    A block wall loaded horizontally by soil bends like a vertically spanning beam, so it cracks along a bed joint near mid-height and bows inward — the classic signature of lateral soil and hydrostatic pressure. Settlement and heave move the wall vertically and produce vertical, diagonal or stair-step cracking instead; the inspector reports the observed condition, notes it as a significant concern, and recommends evaluation by a structural engineer rather than diagnosing the exact cause.

    Ref QB-363SKFSource: National Home Inspector Examination content outline — structural systems: foundation defects and applied forcesReport a problem with this question

  3. 3. An inspector finds stair-step cracking through the mortar joints at one exterior corner of a masonry foundation, wider at the top than at the bottom, together with an out-of-square door frame and a floor that slopes toward that same corner. This pattern most strongly suggests which condition?

    • A.Lateral soil pressure pushing that corner of the wall inward, which racks the framing above it out of square
    • B.Curing shrinkage of the mortar, which opens stepped joints at corners where the masonry dries fastest
    • C.Differential settlement — that corner of the foundation has moved downward relative to the rest of the structure✓ Answer
    • D.Seasonal truss uplift transmitted down through the framing, which pulls the corner and its door frame upward

    Stair-step cracking follows the weakest path through mortar joints when one part of a masonry wall drops relative to another, and a crack that widens toward the top indicates rotation about a lower point, so the corner has settled; the out-of-square door and sloping floor are corroborating interior evidence of the same movement. Lateral pressure produces a horizontal crack with inward bowing, and truss uplift shows as a seasonal gap at the ceiling-wall junction, not foundation cracking.

    Ref QB-JNVKZESource: National Home Inspector Examination content outline — structural systems: foundation movement and crack patternsReport a problem with this question

  4. 4. A poured concrete basement wall in a house less than a year old shows several fine vertical cracks of nearly uniform width, with no offset between the two faces of the crack, no displacement of the wall, and no staining or dampness. What is the most likely explanation?

    • A.Corrosion of reinforcing steel inside the wall, which opens fine vertical cracks along the buried bars
    • B.Shrinkage as the concrete cured; the inspector should still describe the cracks and recommend monitoring✓ Answer
    • C.Hydrostatic pressure from saturated backfill, which cracks a new wall before any dampness appears
    • D.Settlement of the footing under that wall, which first shows as fine vertical cracks in the first year

    Concrete shrinks as it cures and releases that stress as fine cracks of fairly even width with no displacement, typically appearing within the first year and generally not indicating structural movement. Movement cracks differ in that they taper, offset, or displace one side relative to the other, and rebar corrosion announces itself with rust staining and spalling of the concrete cover.

    Ref QB-Y5ZR3CSource: National Home Inspector Examination content outline — structural systems: concrete foundation defectsReport a problem with this question

  5. 5. A house sits on expansive clay soil. Interior drywall cracks at the corners of door openings widen during a long dry period and partially close again after a wet season. Which mechanism best explains this behavior?

    • A.Continued curing shrinkage of the concrete foundation, which keeps opening cracks for many years after construction
    • B.The clay shrinks as it dries and swells as it takes on water, cyclically lowering and raising portions of the foundation✓ Answer
    • C.Thermal expansion and contraction of the framing lumber, which opens joints in hot weather and closes them in cool
    • D.Frost heave of soil water beneath the footings, which lifts the foundation and then lets it settle again

    Expansive clay changes volume with moisture content, so portions of a foundation resting on it rise in wet periods and drop in dry ones, and that seasonal shrink-swell cycle shows up indoors as cracks that open and close with the weather. Frost action requires freezing temperatures rather than dry weather, and neither lumber thermal movement nor concrete curing shrinkage reverses itself seasonally in this way.

    Ref QB-FNTKGBSource: Residential foundation engineering fundamentals — expansive soils and shrink-swell movementReport a problem with this question

  6. 6. In a cold climate, an inspector finds a pier-and-beam house whose masonry piers were set in shallow holes only a short distance below the ground surface. Which mechanism most threatens this foundation?

    • A.Frost heave — water in the soil freezes and expands, lifting the piers, which then settle unevenly when the soil thaws✓ Answer
    • B.Shrink-swell of expansive clay, which the load from each pier drives as it squeezes moisture from the soil
    • C.Hydrostatic pressure from saturated soil collapsing the piers inward, just as it pushes on a basement wall
    • D.Capillary rise carrying moisture up through the piers, which softens the masonry until the piers crush and sink

    Water expands as it freezes, so in frost-susceptible soil the freezing zone lifts anything bearing within it and the support drops unevenly on thaw, producing cyclic movement, cracked masonry and uneven floors. That is precisely why bearing surfaces are placed below the local frost depth, where the soil beneath them does not freeze.

    Ref QB-Z5C49DSource: Residential foundation engineering fundamentals — frost action and depth of bearingReport a problem with this question

  7. 7. An inspector observes a white, crystalline, powdery deposit on the interior face of a masonry basement wall; the wall is dry to the touch at the time of inspection. What is the most accurate interpretation?

    • A.Mold is growing on the wall and remediation should be recommended, since any white surface growth on masonry indicates an established biological colony
    • B.Water has moved through the masonry and evaporated, leaving mineral salts behind — evidence of moisture movement rather than structural damage in itself✓ Answer
    • C.The deposit is freeze-thaw spalling of the masonry surface, in which the face of the block flakes away and leaves a powdery residue behind it
    • D.The wall has lost structural capacity and requires immediate engineering evaluation, because mineral deposits form only where masonry has begun to break down

    Efflorescence is the mineral salt left behind when water migrates through masonry and evaporates at the surface, so it documents that water has been moving through the wall even if the wall is dry today. It is not decay, not mold, and not structural damage; the inspector reports it and looks for the water source, most often exterior grading or roof drainage.

    Ref QB-GN6XNCSource: Residential building science — moisture movement in masonry and efflorescenceReport a problem with this question

  8. 8. A below-grade wall encloses finished living space at a site known to have a high water table. Which statement correctly distinguishes the two common below-grade wall treatments?

    • A.Dampproofing is simply a heavier application of the same material used for waterproofing, so either one is suitable here as long as it goes on the exterior face before the wall is backfilled
    • B.Both treatments are intended only to control water vapor and neither resists liquid water, so footing drainage is the only thing that actually matters at a site like this one
    • C.Dampproofing only resists dampness and vapor where there is no hydrostatic pressure, while a high water table calls for a waterproofing membrane that resists water under pressure✓ Answer
    • D.Waterproofing is applied to the interior face of the wall and dampproofing to the exterior face, so the choice depends on which side of the wall is finished rather than on the water table

    The two treatments are defined by the load they resist: dampproofing is a coating that stops capillary and vapor moisture where water is not standing against the wall, while waterproofing is a continuous membrane system designed to hold back liquid water pushing on the wall. A high water table or other severe soil-water condition therefore calls for the membrane-type treatment plus functioning perimeter drainage.

    Ref QB-W5A4R9Source: Residential building science — below-grade dampproofing versus waterproofingReport a problem with this question

  9. 9. A basement shows staining and efflorescence along the wall-to-floor cove joint on one side of the house only. Outside that same wall, a downspout discharges directly at the foundation and the grade slopes back toward the house. What should the inspector recommend first?

    • A.Correct the roof drainage discharge and the negative grade first, because surface water is the most common source of a wet basement and the least invasive thing to fix✓ Answer
    • B.Install an interior perimeter drain and a sump pump, which collect the water once it has already entered the wall and discharge it away from the house
    • C.Underpin the foundation on that side of the house, since staining along the cove joint indicates that the footing has dropped and opened the joint
    • D.Apply a sealer paint to the interior face of the basement wall, which blocks the visible moisture at the surface and keeps the efflorescence from returning once the wall dries

    The overwhelming majority of wet basements are surface-water problems rather than groundwater problems, and the localized evidence here lines up exactly with the downspout and reverse slope on that one wall. Managing roof runoff and re-establishing fall away from the foundation is the first, least invasive corrective step; interior drainage, sealers or underpinning address symptoms or unrelated conditions and are premature.

    Ref QB-DN4X59Source: National Home Inspector Examination content outline — site grading, drainage and below-grade moistureReport a problem with this question

  10. 10. During a remodel, a heavy point load from an upper floor was brought down onto a post that bears on the finished floor above ordinary floor joists, with no beam, column or footing beneath it in the basement below. What is the principal structural concern?

    • A.The load path is interrupted — a concentrated load must be carried continuously through framing, posts and footings down to the soil, and here it stops at joists that were not designed to receive it✓ Answer
    • B.The only issue is that the post will restrict future use of the basement space, since the framing above it was already sized to carry whatever bears on that floor
    • C.The point load will push the foundation walls outward at the top, because a concentrated load spreads horizontally through the floor system as it travels downward
    • D.Nothing is wrong, because the floor joists will distribute the load evenly to the foundation walls, which is exactly what a repetitive-member floor system is designed to do at any point along the span

    Every load in a building must follow a continuous path — roof to rafters or trusses, to bearing walls and headers, to joists, to girders and columns, to foundation walls and footings, and finally to the soil — and each link must be present and connected. A post landing mid-span on joists breaks that chain and overloads members in bending, and the inspector reports the interrupted load path and recommends evaluation rather than judging how much load the joists can take.

    Ref QB-JDZQDGSource: National Home Inspector Examination content outline — structural systems: load path and vertical supportReport a problem with this question

  11. 11. In a house with conventionally framed rafters and a ridge board, the ties that spanned across the lower portion of the rafter span were removed during an attic conversion. The inspector now finds the exterior walls leaning outward at the top and the ridge line sagging. Why did this happen?

    • A.The ridge board lost its ability to carry the vertical load of the roof once the ties below it were taken out and the rafters began to move
    • B.Those lower ties resisted the outward thrust that rafters exert at their bearing points; without them the rafter feet spread the walls and the ridge drops✓ Answer
    • C.Those were collar ties whose only function was to resist wind uplift at the ridge, so removing them left the roof free to lift and then settle out of line over the seasons
    • D.Removing them reduced dead load, which allowed the roof to rebound upward and drew the tops of the walls outward as the rafters straightened

    Rafters bearing on a ridge board behave as a triangle whose base must be held: rafter ties in the lower third of the span take the horizontal thrust in tension, and cutting them lets the rafters rotate outward, spreading the walls and dropping the ridge. Collar ties are a different member, located in the upper third near the ridge, and they resist uplift and ridge separation rather than thrust.

    Ref QB-3W6WYGSource: National Home Inspector Examination content outline — structural systems: roof and ceiling framingReport a problem with this question

  12. 12. What distinguishes a structural ridge beam from a ridge board in conventional roof framing?

    • A.A ridge beam is used only on hip roofs and a ridge board only on gable roofs, so the choice follows the shape of the roof rather than how the load is carried down
    • B.A ridge beam carries roof load down posts to bearing, so the walls see no outward thrust; a ridge board is only a nailing surface, and ties must resist the thrust✓ Answer
    • C.The two terms describe the same member and are used interchangeably, since any framing member at the ridge performs the same job once the rafters are nailed to it
    • D.A ridge board carries the roof load while a ridge beam merely aligns the tops of the rafters, which is why a ridge board must be supported by posts at each end

    A ridge board does not carry vertical load; it only aligns and provides a nailing surface for opposing rafters, so the rafter pair acts as a triangle and needs ties at the bottom to resist outward thrust. A structural ridge beam does carry load and transfers it through posts to a continuous load path, so the rafters bear on it rather than pushing the walls apart, and mislabeling one for the other leads to missing the need for ties.

    Ref QB-KDC3KHSource: National Home Inspector Examination content outline — structural systems: roof and ceiling framingReport a problem with this question

  13. 13. An inspector finds that a web member of an engineered roof truss has been cut through so that a duct could pass. What is the appropriate response?

    • A.Calculate the truss's remaining capacity and state in the report whether it is still adequate, since the inspector saw the cut member and can measure what is left of it
    • B.Note it as a minor workmanship item, since web members carry little load compared with the top and bottom chords that span between the bearing points
    • C.Recommend sistering the cut web with a piece of dimensional lumber of the same size, because matching the original member restores the load path through the truss
    • D.Report it as a significant structural defect and recommend that a repair be designed by a qualified engineer or the truss manufacturer's designer✓ Answer

    A truss is an engineered system in which every chord and web carries a specific tension or compression force, so cutting any member redistributes forces the assembly was never designed for and can lead to progressive failure. The inspector's role is to describe the condition and refer it to the truss designer or an engineer; specifying a field repair or computing remaining capacity would be engineering work outside the scope of a visual home inspection.

    Ref QB-4WH86JSource: Home inspection standards of practice — reporting defects and recommending further evaluationReport a problem with this question

  14. 14. A homeowner reports that a horizontal gap opens between the ceiling and the interior partition walls each winter and closes again in summer. The roof is framed with engineered trusses. What is the most likely explanation?

    • A.Truss uplift — seasonal moisture differences between the top and bottom chords arch the bottom chord upward; it is a serviceability and cosmetic issue rather than a structural failure✓ Answer
    • B.The foundation settles each winter and rebounds each summer, so the ceiling stays put while the partition walls below it rise and fall with the soil
    • C.The bottom chord of the truss has failed in tension, allowing the truss to sag away from the partition walls each winter and then recover again as the loads carried by the roof change through the summer
    • D.Snow load has permanently deflected the roof structure, pressing the trusses down onto the partitions in winter and releasing them once the roof clears

    When the top chord sits in cold, damp attic air while the bottom chord stays warm and dry above the insulation, the differing moisture content makes the bottom chord bow upward, lifting the ceiling off non-bearing partitions until conditions reverse. The pattern is seasonal and reversible, which distinguishes it from settlement or a failed member, and it is reported as a cosmetic and serviceability condition.

    Ref QB-GDA33ESource: Residential roof framing behavior — seasonal truss upliftReport a problem with this question

  15. 15. Two identical floor joists of the same span have each had material removed at mid-span: one has a notch cut into its bottom edge, the other has a round hole bored near mid-depth. Why is the notch the greater structural concern?

    • A.Round holes never reduce a joist's capacity, regardless of their size or their location, because the wood simply redistributes stress around the circular opening
    • B.Notches matter only because they expose end grain and encourage decay, while the loss of cross-section at mid-span has no measurable effect on bending strength
    • C.The bottom of a joist is in compression and wood is weakest in compression, so removing material from the compression face is what governs the loss of capacity
    • D.Bending puts the bottom fibers at mid-span in maximum tension, so a notch removes the most stressed wood, while wood near mid-depth carries little stress✓ Answer

    In a simply supported bending member the extreme fibers are the most stressed — bottom in tension and top in compression at mid-span — and stress falls to nearly zero at the neutral axis in the middle of the depth. Removing tension-zone material at mid-span therefore costs far more capacity than a hole placed near the neutral axis, and the sharp inside corner of a notch adds a crack-initiating stress concentration; this principle, not a memorized fraction, is what tells an inspector which cut to flag.

    Ref QB-ZVF8NESource: Structural mechanics of bending members — principles behind notching and boring limitsReport a problem with this question

  16. 16. In a basement, an inspector finds an adjustable steel screw post supporting a built-up wood girder. The post is not fastened at the top or the bottom, it bears directly on the basement floor slab with no separate footing pad, and its base is corroded where the slab is damp. What should the inspector do?

    • A.Report only the corrosion, since an unfastened post is normal for adjustable columns and the load itself holds the post tight against the girder above it
    • B.Determine the size of footing pad that is required and specify it in the report, since sizing that pad is the single correction that would resolve every condition observed at this post
    • C.Consider the arrangement acceptable, because the floor slab distributes the load to the soil and a slab poured over compacted fill will carry a column point load
    • D.Describe these conditions as defects affecting the support and lateral stability of the girder and recommend evaluation and correction by a qualified contractor or engineer✓ Answer

    A column is part of the load path only if it is positively connected at the top and base and bears on a footing sized for the load; a floor slab is not a footing, an unconnected post can shift or be displaced laterally, and base corrosion signals persistent slab moisture that will continue. The inspector describes the observed deficiencies and refers them out, because determining the required footing or the adequacy of the support is beyond a visual inspection.

    Ref QB-HDND8FSource: National Home Inspector Examination content outline — structural systems: columns, beams and connectionsReport a problem with this question

  17. 17. A floor feels noticeably springy underfoot, but the visible joists and girder show no sagging, cracking, decay, or loss of bearing. What is the best way for the inspector to handle this?

    • A.State in the report that the joists are undersized and specify sistering as the required repair, because bounce underfoot is a direct measure of insufficient joist depth for the span in question
    • B.Leave the observation out of the report, since a springy floor is not a failure and nothing visible on the framing supports calling it a defect
    • C.Calculate the joist span and publish the allowable load for the floor in the report, so the client has a number to compare against the furniture they intend to place
    • D.Describe the observed bounce as a stiffness and serviceability concern, recommend further evaluation, and note that a visual inspection does not determine the adequacy of framing sizes or spans✓ Answer

    Excessive deflection is a stiffness and serviceability problem that can exist while the members are still strong enough not to fail, so it is a real, reportable observation even without visible damage. Standards of practice describe a home inspection as visual and not technically exhaustive and exclude determining the adequacy of structural systems, spans and member sizes, so the correct report language states the condition and refers it out rather than sizing a repair.

    Ref QB-2WTJTFSource: Home inspection standards of practice — scope, limitations and exclusionsReport a problem with this question

  18. 18. In a hot, humid climate an inspector finds a vented crawl space with condensation and surface mold on cool duct surfaces and on the underside of the floor during summer, while the same crawl space is dry in winter. What is the most likely mechanism?

    • A.A plumbing supply line is leaking on a seasonal cycle, releasing water only during the warmer months and drying out again once the weather turns cold
    • B.The crawl space simply has too few vents, and adding more openings will resolve the problem by carrying the excess summer moisture back out to the exterior air where it can disperse
    • C.Warm, humid outdoor air entering the vents condenses on surfaces that are colder than its dew point, so ventilation can add moisture in this climate rather than remove it✓ Answer
    • D.Groundwater seeps through the foundation walls only during the summer months, wetting the soil and the framing above it until the water table falls again

    Air can hold less water vapor as it cools, so humid summer air drawn into a crawl space that is chilled by the ground and by cold ducts reaches its dew point and deposits liquid water on those surfaces, feeding mold. This is why in humid climates a vented crawl space can be a moisture source and adding vents typically makes it worse; the corrective direction is ground moisture control and a sealed, conditioned or dehumidified crawl space.

    Ref QB-PDE34NSource: Residential building science — crawl space ventilation and condensationReport a problem with this question

  19. 19. In a crawl space, an inspector finds scrap lumber and buried form boards lying on the soil, a girder end only a few inches above exposed earth, and a ground vapor retarder that is torn and pushed aside. No insects, tubes or fungal growth are visible. How should these findings be handled?

    • A.Report them as evidence of an active infestation and state that chemical treatment is required, because scrap wood lying in contact with soil means insects are already present
    • B.Report only the torn vapor retarder, treating the debris as a housekeeping matter that the seller can clear out before closing without any further comment
    • C.Report them as conditions conducive to wood-destroying organisms and decay, because together they supply the moisture, cellulose and earth contact those organisms require✓ Answer
    • D.Omit them from the report, since no organisms or damage were actually observed and a visual inspection can only describe conditions that are already visible

    Reporting "conditions conducive" is exactly what a home inspector does: cellulose debris on the ground, earth-to-wood proximity and an interrupted ground vapor retarder together create the damp, food-rich, soil-connected environment that decay fungi and wood-destroying insects need, whether or not organisms are present today. Declaring an active infestation or prescribing treatment goes beyond the visual scope and belongs to a qualified pest specialist.

    Ref QB-7WK8PNSource: National Home Inspector Examination content outline — conditions conducive to wood-destroying organismsReport a problem with this question

  20. 20. Which statement about fungal decay in structural wood is correct?

    • A."Dry rot" is decay that occurs in genuinely dry wood, so controlling moisture cannot stop it and the only effective response is to replace the affected members
    • B.Surface mold and mildew on framing are the first stage of structural decay and directly reduce the strength of the wood, so any visible growth means capacity has been lost
    • C.Decay fungi need wood that stays wet, roughly above 20 percent moisture, so "dry rot" is a misnomer, and drying the wood and removing the water source stops further decay✓ Answer
    • D.Decay fungi need only warmth and oxygen; the moisture content of the wood is unrelated to whether decay progresses, which is why drying a member does not slow it down

    Decay fungi need four things at once — cellulose to eat, oxygen, a favorable temperature, and free water in the wood — and removing any one of them stops the process, which is why moisture control is the practical cure. The term "dry rot" describes wood that decayed while wet and later dried, not decay of dry wood; surface mold, by contrast, is a staining and indoor-air issue that does not consume the wood's structure.

    Ref QB-WNQKY8Source: Wood durability fundamentals — decay fungi and wood moisture contentReport a problem with this question

  21. 21. In a crawl space an inspector finds galleries excavated in a sill plate that are smooth and clean, free of soil, with coarse sawdust-like debris on the ground below and no earthen tubes anywhere on the foundation. Compared with subterranean termite damage, this pattern is best characterized how?

    • A.Not reportable at all, because insect evidence lies entirely outside the scope of a home inspection and belongs only in a separate wood-destroying-organism report
    • B.Identical to subterranean termite damage, which also leaves clean, soil-free galleries and no tubes, so the two cannot be told apart from the galleries alone
    • C.Proof of powderpost beetles, which leave large open galleries and never produce exit holes, so the coarse debris below is frass pushed out of the gallery ends
    • D.More consistent with carpenter ants, which excavate wood to nest rather than eat it; report the evidence and conducive conditions and refer to a pest specialist✓ Answer

    Subterranean termites keep contact with soil and pack their galleries with soil and fecal material, leaving layered, soil-flecked damage and shelter tubes over foundations and piers, while carpenter ants only nest in wood softened by moisture and leave galleries that look smooth and swept, with coarse frass pushed out below. A general home inspection is not a wood-destroying-organism inspection, so the inspector reports what is visible and the conditions conducive to it and defers identification and treatment to a qualified pest professional.

    Ref QB-D6JED8Source: Wood-destroying organism evidence — damage characteristics and inspector referralReport a problem with this question

  22. 22. On a new house, an inspector checks the 1/2-in. anchor bolts that secure the wood sill plate to a poured concrete foundation. Which layout meets the minimum anchorage rule of IRC 2021 for each sill plate section?

    • A.Bolts no more than 8 ft apart, with one within 24 in. of each plate end
    • B.Bolts no more than 10 ft apart, with one within 12 in. of each plate end
    • C.Bolts no more than 6 ft apart, with one within 12 in. of each plate end✓ Answer
    • D.Bolts no more than 6 ft apart, with one within 36 in. of each plate end

    IRC 2021 R403.1.6 requires sill plates to be anchored with bolts of at least 1/2-in. diameter spaced not more than 6 ft on center, extending at least 7 in. into the concrete, with at least two bolts per plate section and one bolt not more than 12 in. (and not less than seven bolt diameters) from each end. The plate ends are where sliding and uplift forces concentrate, so wider spacing or a bolt set far back from the end leaves the plate under-anchored and should be reported.

    Ref QB-XN3X5ASource: IRC 2021 Section R403.1.6 Foundation anchorage (codes.iccsafe.org, IRC2021P2 Chapter 4)Report a problem with this question

  23. 23. A vented crawl space has 1,500 sq ft of under-floor area, and the exposed soil is fully covered with an approved Class I vapor retarder. Under IRC 2021, what is the minimum total net area of the ventilation openings?

    • A.10 sq ft
    • B.1 sq ft✓ Answer
    • C.5 sq ft
    • D.15 sq ft

    IRC 2021 R408.2 sets the basic requirement at 1 sq ft of net vent area per 150 sq ft of under-floor area (10 sq ft here), but Exception 1 allows the total to be reduced to 1/1,500 of the under-floor area when the ground is covered with an approved Class I vapor retarder, which gives 1 sq ft. The retarder blocks the soil, the main moisture source, so much less ventilation is needed. The 5 and 15 sq ft figures come from ratios that R408.2 does not use.

    Ref QB-E6WRJ9Source: IRC 2021 Section R408.2 Openings for under-floor ventilation, Exception 1 (codes.iccsafe.org, IRC2021P2 Chapter 4)Report a problem with this question

  24. 24. In a crawl space, an inspector measures an untreated wood girder 10 in. above exposed soil and untreated floor joists 20 in. above the soil. Neither member is naturally durable wood. How should these clearances be evaluated under IRC 2021?

    • A.Both are acceptable; untreated framing needs only 8 in. of clearance
    • B.The joists are too low; joists need 24 in. and girders need 18 in.
    • C.Both are too low; all untreated floor framing needs 24 in. of clearance
    • D.The girder is too low; girders need 12 in. and joists need 18 in.✓ Answer

    IRC 2021 R317.1 item 1 requires naturally durable or preservative-treated wood in crawl spaces where joists are closer than 18 in. to exposed ground and where girders are closer than 12 in. The joists at 20 in. comply, but the untreated girder at 10 in. is within the decay zone and should be reported for correction. The 8-in. figure applies to wood columns and to framing on exterior foundation walls, not to girders and joists over crawl space soil.

    Ref QB-UNZWM6Source: IRC 2021 Section R317.1 Location required, item 1 (codes.iccsafe.org, IRC2021P2 Chapter 3)Report a problem with this question

  25. 25. To pass a drain line, a plumber cut a notch 1 in. deep into the top edge of a 2x10 sawn-lumber floor joist at the center of its span. The notch is less than 1/6 of the joist depth. Why is it still a defect under IRC 2021?

    • A.Notches are not permitted in the middle third of the span✓ Answer
    • B.Notches in a top edge may not exceed 1/2 in. in depth
    • C.Notches are permitted only within 12 in. of a bearing wall
    • D.Notches are not permitted anywhere in a sawn floor joist

    IRC 2021 R502.8.1 limits notches in sawn lumber joists to 1/6 of the depth and 1/3 of the depth in length, and prohibits them in the middle third of the span; end notches may go to 1/4 of the depth. The middle of the span is where bending stress is highest, so removing material there cuts capacity even when the notch is shallow. The inspector should report it and recommend repair by a qualified contractor or evaluation by an engineer.

    Ref QB-B6UR26Source: IRC 2021 Section R502.8.1 Sawn lumber (cutting, drilling and notching) (codes.iccsafe.org, IRC2021P2 Chapter 5)Report a problem with this question

  26. 26. An electrician needs to bore a hole through a sawn-lumber floor joist whose actual depth is 9 in. Which hole meets the IRC 2021 limits for bored holes in joists?

    • A.2 1/4 in. diameter, at least 5/8 in. from the top and bottom edges
    • B.3 in. diameter, at least 2 in. from the top and bottom edges✓ Answer
    • C.4 1/2 in. diameter, at least 1 in. from the top and bottom edges
    • D.1 1/2 in. diameter, at least 1/2 in. from the top and bottom edges

    IRC 2021 R502.8.1 limits bored holes in sawn lumber joists to one-third of the member depth (3 in. for a 9-in. joist) and requires them to be at least 2 in. from the top or bottom edge and from any other hole or notch. Keeping holes near mid-depth places them close to the neutral axis, where bending stress is lowest. The 5/8-in. edge distance is the stud boring rule in R602.6, not the joist rule, and a hole half the joist depth is far over the limit.

    Ref QB-VNC9T7Source: IRC 2021 Section R502.8.1 Sawn lumber (bored hole limits) (codes.iccsafe.org, IRC2021P2 Chapter 5)Report a problem with this question

  27. 27. In a basement, an inspector sees floor joist ends resting directly on a ledge of the poured concrete foundation wall with only about 1 1/2 in. of bearing, and no joist hangers or ledger. How should this be evaluated under IRC 2021?

    • A.Acceptable; joists need only 1 1/2 in. of bearing on concrete
    • B.Deficient; joists need at least 4 in. of bearing on concrete
    • C.Acceptable; joists need only 1 in. of bearing on any support
    • D.Deficient; joists need at least 3 in. of bearing on concrete✓ Answer

    IRC 2021 R502.6 requires the ends of each joist, beam or girder to have at least 1 1/2 in. of bearing on wood or metal and at least 3 in. on masonry or concrete, or to be supported by approved joist hangers. The 1 1/2-in. figure is the wood-or-metal minimum, so applying it to concrete is a common mistake. Short bearing on concrete risks crushing or spalling at the edge and the joist slipping off, so the inspector should report it as a structural deficiency.

    Ref QB-C67487Source: IRC 2021 Section R502.6 Bearing (codes.iccsafe.org, IRC2021P2 Chapter 5)Report a problem with this question

  28. 28. In an exterior bearing wall, an inspector finds a single 2x4 stud (3 1/2 in. deep) with a 2-in. hole bored through its center for a drain pipe. Each edge of the hole is 3/4 in. from the stud face. How should this be evaluated under IRC 2021?

    • A.Acceptable; holes up to 60 percent are allowed in any single stud
    • B.Defect; holes in bearing-wall studs may never exceed 25 percent
    • C.Defect; a bearing stud bored over 40 percent must be doubled✓ Answer
    • D.Acceptable; the 5/8 in. edge distance is the only limit that applies

    A 2-in. hole in a 3 1/2-in. stud removes about 57 percent of its depth. IRC 2021 R602.6 allows bored holes up to 60 percent with at least 5/8 in. to the edge, but where a stud in an exterior wall or bearing partition is bored over 40 percent, the stud must be doubled, and no more than two successive doubled studs may be so bored. A single bored stud therefore loses too much axial capacity and should be reported. The 25 percent figure is the notching limit for bearing studs, not the boring limit.

    Ref QB-SNA9A4Source: IRC 2021 Section R602.6 Drilling and notching of studs, item 2 Boring (codes.iccsafe.org, IRC2021P2 Chapter 6)Report a problem with this question

  29. 29. The door between an attached garage and the kitchen is a hollow-core wood interior door with no closer. Under IRC 2021, what should the inspector report?

    • A.Defect; it needs a solid or fire-rated door that self-closes and self-latches✓ Answer
    • B.Acceptable; any door is allowed if the garage has a working smoke alarm
    • C.Defect; it needs a 90-minute rated door, but a closer is not required
    • D.Acceptable; only doors from the garage into a bedroom are regulated

    IRC 2021 R302.5.1 requires openings between the garage and the residence to have a solid wood door at least 1 3/8 in. thick, a solid or honeycomb-core steel door at least 1 3/8 in. thick, or a 20-minute fire-rated door, and the door must be self-latching with a self-closing or automatic-closing device. A hollow-core door with no closer breaks the garage fire separation and lets fire and exhaust gases into the house. Openings from a garage directly into a sleeping room are not merely regulated but prohibited.

    Ref QB-9654Q3Source: IRC 2021 Section R302.5.1 Opening protection (codes.iccsafe.org, IRC2021P2 Chapter 3)Report a problem with this question

  30. 30. In a conventionally framed attic, an inspector sees 1x4 boards nailed across opposing rafters, spaced 4 ft on center. The client asks where collar ties belong. Under IRC 2021, where must collar ties be located?

    • A.In the lower third of the attic, near the top plates
    • B.In the upper third of the attic, near the ridge✓ Answer
    • C.In the middle third of the attic, at mid-rafter
    • D.At any height, as long as each rafter pair is tied

    IRC 2021 R802.4.6 requires collar ties, where used, to be in the upper third of the attic space, at least 1x4 nominal and not more than 4 ft on center; ridge straps may replace them. Ties low in the attic are a different member: ceiling joists or rafter ties that keep the rafters from spreading the walls outward (R802.3 refers to them as the continuous ties). A collar tie high up does not resist that outward thrust, so it is never a substitute for missing or cut rafter ties.

    Ref QB-TKQEF5Source: IRC 2021 Section R802.4.6 Collar ties (codes.iccsafe.org, IRC2021P2 Chapter 8)Report a problem with this question

  31. 31. In an attic framed with engineered roof trusses, an inspector finds that a new air handler and a storage platform were placed on the truss bottom chords. No truss design or engineering documents are available. What is the best recommendation?

    • A.Accept it; truss bottom chords are designed for any attic equipment load
    • B.Accept it if the platform spans at least three trusses to share the load
    • C.Report it; have a design professional verify the trusses can carry the load✓ Answer
    • D.Report it; have a carpenter add plywood gussets to stiffen each chord

    IRC 2021 R802.10.4 states that alterations adding load, such as HVAC equipment or a water heater, that exceed the truss design load are not permitted without verification that the truss can support the added load, and that truss members may not be cut, spliced or otherwise altered without a registered design professional's approval. Bottom chords are often designed for only a light ceiling and limited storage load, and spreading the load over more trusses does not prove capacity. Field-added gussets are themselves an unapproved alteration, so the right step is to report and refer for engineering verification.

    Ref QB-B4WK26Source: IRC 2021 Section R802.10.4 Alterations to trusses (codes.iccsafe.org, IRC2021P2 Chapter 8)Report a problem with this question

  32. 32. On a sloping lot, a freestanding retaining wall that is not part of the house foundation and is not braced at the top holds back about 6 ft of unbalanced soil. It leans outward and shows open cracks. Which response best reflects IRC 2021?

    • A.Only walls that support the house need design; note it as yard upkeep
    • B.Walls over 96 in. of fill need design; note it for routine monitoring
    • C.Any wall over 36 in. must be rebuilt in concrete; refer to a mason
    • D.Walls over 48 in. of fill need engineered design; refer to an engineer✓ Answer

    IRC 2021 R404.4 requires retaining walls that are not laterally supported at the top and retain more than 48 in. of unbalanced fill to be designed by accepted engineering practice for stability against overturning, sliding, excessive foundation pressure and water uplift, with a safety factor of 1.5. This 6-ft wall is in that category, and outward lean with open cracks shows overturning movement already under way. The inspector reports the condition and its implication and refers it to a structural engineer rather than prescribing a repair; the section expressly excludes foundation walls that support buildings, not freestanding walls.

    Ref QB-SKC4A4Source: IRC 2021 Section R404.4 Retaining walls (codes.iccsafe.org, IRC2021P2 Chapter 4)Report a problem with this question

  33. 33. Around a house with no lot-line or slope constraints, an inspector measures that the soil falls only about 2 in. over the first 10 ft from the foundation, and the basement shows dampness along that wall. What minimum grade does IRC 2021 require?

    • A.A fall of at least 6 in. within the first 10 ft✓ Answer
    • B.A fall of at least 2 in. within the first 10 ft
    • C.A fall of at least 12 in. within the first 10 ft
    • D.A fall of at least 1 in. within the first 10 ft

    IRC 2021 R401.3 requires lots to be graded to drain surface water away from foundation walls, with a fall of not fewer than 6 in. within the first 10 ft; where physical barriers prevent that, drains or swales must carry water away, and impervious surfaces within 10 ft must slope at least 2 percent away. The 2-in. distractor resembles the 2 percent paved-surface slope (about 2.4 in. over 10 ft), which does not apply to soil. A flat grade lets water collect against the wall, raising hydrostatic pressure and causing the dampness seen, so the inspector should report it and recommend regrading.

    Ref QB-A4J9V4Source: IRC 2021 Section R401.3 Drainage (codes.iccsafe.org, IRC2021P2 Chapter 4)Report a problem with this question

Other topics in this exam

Practice questions based on the National Home Inspector Examination content outline, widely shared home inspection standards of practice, and residential building science. Not affiliated with or endorsed by any examination board, licensing authority, or inspector association. A home inspection is a visual, non-invasive examination and is not a code-compliance inspection — nothing here should be read as a code requirement. Home inspection is regulated differently from place to place; confirm your own jurisdiction's requirements and the standards of practice you are held to before testing or inspecting. About the National Home Inspector Examination →