29 HVAC Service & When to Refer Practice Questions & Answers
Every HVAC Service & When to Refer practice question from the CAMT Apartment Maintenance Practice Test, with the correct answer and a short explanation.
Start practice test →1. A technician replaces the return-air filter in an apartment air handler and notices an arrow printed on the filter frame. How should the filter be positioned in the rack?
- A.With the arrow facing the access panel so the size stays readable
- B.With the arrow pointing away from the blower, back toward the return grille
- C.With the arrow pointing toward the blower, in the direction air travels✓ Answer
- D.With the arrow pointing upward regardless of how the cabinet is mounted
The arrow marks the direction air travels through the media, so it must point toward the blower. The filter carries its reinforced backing on the downstream face so the media cannot bow under the pull of the blower; installed backwards it can deform, tear, and let dirt pass through onto the evaporator coil.
Ref QB-NXVJFYSource: NAAEI Certificate for Apartment Maintenance Technicians, HVAC Maintenance and RepairReport a problem with this question
2. An apartment air conditioner has gone a long time without a filter change and the filter is matted with dust. Beyond poor air circulation, what is the technician most likely to find if the condition continues?
- A.Reduced airflow across the coil, which can ice the coil and strain the blower✓ Answer
- B.A colder supply air stream, because less air passes over the cold coil surface
- C.Higher airflow at the registers, because air is forced through a smaller area
- D.Cleaner coils, because the loaded filter captures more of the dust in the air
A loaded filter restricts return airflow, so less air crosses the evaporator coil. With too little heat picked up from the air, the coil surface falls below freezing and ice forms, while the blower works against higher resistance. The same restriction in heating lets the heat exchanger overheat.
Ref QB-4FC3QWSource: NAA CAMT Skill Checks with Answer Key, Air Conditioning Maintenance and RepairReport a problem with this question
3. The correct filter size for an apartment air handler is out of stock, and a slightly smaller filter is on the shelf. A technician considers wedging it into the rack. Why is this the wrong choice?
- A.A smaller filter raises static pressure and starves the return duct of air
- B.A smaller filter cannot hold its shape and will be pulled into the return grille
- C.An undersized filter blocks the condensate drain opening inside the blower cabinet
- D.Air bypasses around the edges of the filter and carries dirt onto the coil✓ Answer
A filter only cleans the air that is forced through it. Any gap at the edge of the rack becomes the path of least resistance, so unfiltered air slips past and deposits dirt on the evaporator coil, where the film of dirt insulates the coil and cuts heat transfer. Order the correct size rather than improvise.
Ref QB-MXH8AXSource: NAAEI Certificate for Apartment Maintenance Technicians, HVAC Maintenance and RepairReport a problem with this question
4. A resident on a lower floor reports a brown stain spreading across the bedroom ceiling. The apartment directly above has its air handler in a closet over that bedroom, and the air conditioner is running. What should the technician check first?
- A.The refrigerant line insulation where it enters the upstairs wall
- B.The condensate drain line, drain pan and pan overflow, for a blockage✓ Answer
- C.The domestic water supply line feeding the upstairs bathroom fixtures
- D.The roof flashing above the upstairs unit for wind-driven rain damage
A running evaporator coil condenses water continuously, and that water must leave through the drain pan and drain line. When the line or the pan outlet clogs, the pan fills and spills into the ceiling cavity below, which is exactly how a blocked condensate line first shows up as a stain in the apartment underneath.
Ref QB-7FE382Source: NAAEI Certificate for Apartment Maintenance Technicians, HVAC Maintenance and RepairReport a problem with this question
5. A resident reports the air conditioner suddenly stopped running. The thermostat display works, the breaker is on, and the technician finds standing water in the pan under the air handler. What is the most likely explanation?
- A.The compressor overload tripped because the pan lost its water seal
- B.The blower motor seized after water reached the return air filter rack
- C.The thermostat lost its batteries and cannot send a call for cooling
- D.The pan float switch opened the control circuit to stop water damage✓ Answer
A float or overflow switch sits in the pan and opens the low-voltage control circuit when water rises, deliberately shutting the equipment down before the water can reach the ceiling below. The thermostat still has power, which is why it looks normal. The technician clears the drain, empties the pan, and confirms the switch resets.
Ref QB-QXK8T2Source: NAAEI Certificate for Apartment Maintenance Technicians, HVAC Maintenance and RepairReport a problem with this question
6. The condensate drain line leaving an air handler includes a trap near the cabinet. What is the purpose of that trap?
- A.It keeps cabinet air pressure from blowing or pulling through the drain line✓ Answer
- B.It slows the water down so the drain line cannot overflow at the pan
- C.It collects sediment so the outdoor end of the line stays clear
- D.It vents sewer gas away from the closet where the unit is installed
The drain pan sits inside a cabinet that the blower holds at a pressure different from the room. Without a water seal in the trap, that pressure difference pushes or pulls air through the drain line instead of letting water run out, so the pan backs up and eventually overflows even though nothing is clogged.
Ref QB-6F3R2ZSource: NAAEI Certificate for Apartment Maintenance Technicians, HVAC Maintenance and RepairReport a problem with this question
7. Water is dripping from the small auxiliary drain line that ends above a window on the outside of the building. What does this tell the technician?
- A.The secondary pan has cracked and the whole pan must be replaced now
- B.The primary condensate drain is blocked and needs to be cleared✓ Answer
- C.The condensate pump has failed and must be replaced right away
- D.The auxiliary line was routed too low and should be re-piped upward
The auxiliary or secondary drain is a backup that carries no water at all when the system is healthy. It is deliberately terminated somewhere conspicuous so that visible dripping serves as an early warning that the primary drain has stopped working, before water finds the ceiling instead.
Ref QB-PX8WMZSource: NAAEI Certificate for Apartment Maintenance Technicians, HVAC Maintenance and RepairReport a problem with this question
8. A resident complains the apartment never gets cool and the unit runs all day. The technician finds a tall bookcase pushed flat against the return-air grille in the hallway. What is the correct next step?
- A.Close half of the supply registers to push more air to the bedroom areas
- B.Clear the space at the return grille and tell the resident why✓ Answer
- C.Call the HVAC contractor to add a second return grille in the hallway
- D.Set the thermostat fan switch to ON so the blower never stops running
The blower can only deliver the air it is able to draw in. A blocked return starves the system, so the coil gets too little airflow, capacity drops, and the unit runs continuously without satisfying the thermostat. This is a routine service fix, and telling the resident why keeps the obstruction from returning.
Ref QB-ZEA37TSource: NAA CAMT Skill Checks with Answer Key, Air Conditioning Maintenance and RepairReport a problem with this question
9. During a turn, a technician finds supply registers in two vacant bedrooms closed and a balancing damper in the trunk duct nearly shut. Why does this matter for the cooling system?
- A.Closed registers raise the return air temperature and shorten each cycle
- B.Closed registers force the condenser fan to run at a higher speed
- C.Closed dampers cause the thermostat to switch itself into heating
- D.Total airflow through the equipment drops, reducing cooling capacity✓ Answer
Closing registers and dampers does not redirect air for free; it adds resistance and the blower simply moves less air overall. Less air across the evaporator coil means less heat is absorbed, capacity falls and the coil can ice. A turn inspection should reopen registers and restore dampers to their balanced position.
Ref QB-HXF8STSource: NAAEI Certificate for Apartment Maintenance Technicians, HVAC Maintenance and RepairReport a problem with this question
10. During seasonal maintenance a technician finds the outdoor condensing unit packed with grass clippings and surrounded by shrubs grown against the cabinet. What is the effect on the system, and the correct action?
- A.Heat cannot leave the coil; clean the coil and cut back the clearance✓ Answer
- B.Cold air cannot enter the coil; wrap the cabinet to hold heat inside it
- C.The fan reverses direction; replace the fan motor and clear the shrubs
- D.The coil freezes solid; wash it with a strong solvent and restart the unit
The condenser's whole job is to reject the heat picked up indoors, and it does that by passing outdoor air across its fins. Clippings and shrubs block that air, so the heat has nowhere to go, capacity falls and the unit runs long. Cleaning the coil and restoring clearance around the cabinet is routine preventive maintenance.
Ref QB-X9R9TESource: NAA CAMT Skill Checks with Answer Key, Air Conditioning Maintenance and RepairReport a problem with this question
11. A technician opens an air handler closet and finds the evaporator coil covered in a solid block of ice while the system is calling for cooling. What is the correct next step?
- A.Leave the unit running so the ice melts while the apartment keeps cooling
- B.Switch cooling off, run the fan to thaw the coil, then check filter and airflow✓ Answer
- C.Aim a heat gun at the coil until the ice clears and then close the panel
- D.Chip the ice off the coil with a screwdriver and restore the unit to service
Ice blocks the fins so no air can pass, and nothing about the system can be judged until it is gone. Running the blower with cooling off melts the ice safely, and the technician then looks for the airflow causes within a maintenance technician's scope, a dirty filter, blocked return or dirty coil, and refers the unit if airflow proves normal.
Ref QB-ESJ48ESource: NAAEI Certificate for Apartment Maintenance Technicians, HVAC Maintenance and RepairReport a problem with this question
12. A resident reports no cooling. The technician arrives and the thermostat display is blank. What should be checked before assuming the equipment has failed?
- A.The condensate drain line for standing water at the outside end
- B.The condenser fan blade for damage from debris in the cabinet
- C.Thermostat batteries and the power supplied to the thermostat✓ Answer
- D.The supply registers in every room for a closed damper blade
A blank display means the control has no power, and a control that cannot send a call for cooling produces exactly the same complaint as broken equipment. Restoring thermostat power is inside routine service, and checking it first prevents an unnecessary contractor call for a unit that is perfectly sound.
Ref QB-Y94MYFSource: NAAEI Certificate for Apartment Maintenance Technicians, HVAC Maintenance and RepairReport a problem with this question
13. A resident complains the living room is uncomfortable and the system short cycles. The technician sees the thermostat mounted directly above a floor lamp and close to a supply register. Why is this a problem?
- A.The thermostat wiring picks up interference from the lamp circuit nearby
- B.The thermostat batteries drain faster from the warm air rising past it
- C.The thermostat senses local heat and air, not true room temperature✓ Answer
- D.The thermostat loses its low-voltage signal when the register is open
A thermostat controls the system from the air touching its sensor, so it must sit where that air represents the room. Heat rising from the lamp makes it call when the room is already comfortable, and cold supply air blowing on it makes it satisfy early, which is what produces the short cycling and the complaint.
Ref QB-FSWEDFSource: NAAEI Certificate for Apartment Maintenance Technicians, HVAC Maintenance and RepairReport a problem with this question
14. A resident says the vents blow air all the time but the air is not always cold, and asks the technician to fix the unit. The thermostat fan switch is set to ON. What should the technician do?
- A.Leave the switch on ON and schedule a contractor to inspect the system
- B.Explain the setting, move the fan switch to AUTO, and verify cooling✓ Answer
- C.Turn the system off at the breaker until a contractor can look at it
- D.Leave the switch on ON and replace the thermostat with a new one
With the fan switch on ON the blower runs continuously, including during the long stretches when the cooling side is off, so room-temperature air keeps coming out of the registers. In AUTO the blower runs only with a call for cooling. This is a control-setting complaint, not an equipment fault, and it is resolved on the spot.
Ref QB-Z9FX5HSource: NAAEI Certificate for Apartment Maintenance Technicians, HVAC Maintenance and RepairReport a problem with this question
15. A technician calls a work order in to an HVAC contractor and reports that the unit is not blowing any air at all, although the outdoor unit is running. Which component's job is the technician describing as failing?
- A.The compressor, which raises the pressure of the refrigerant vapor
- B.The condenser, which rejects heat from the refrigerant outdoors
- C.The metering device, which controls refrigerant flow into the coil
- D.The blower, which moves return air out through the supply ducts✓ Answer
Moving air is the blower's function: it draws air from the return plenum and pushes it across the coil and out through the supply ducts. Naming the failing function correctly, rather than guessing at a refrigerant problem, tells the contractor to arrive prepared for the indoor air-moving side of the system.
Ref QB-GS9SJGSource: NAA CAMT Skill Checks with Answer Key, Air Conditioning Maintenance and RepairReport a problem with this question
16. During preventive maintenance on a belt-drive blower, the technician hears a squeal at start-up and finds the belt glazed and loose. What is the appropriate action for a maintenance technician?
- A.Leave the belt alone and log it for the contractor's seasonal visit
- B.Tighten the belt as far as the adjustment allows while it is running
- C.Spray belt dressing on the running belt to quiet the squeal for now
- D.Lock out power, then replace the belt and set the tension correctly✓ Answer
A glazed, loose belt slips on the sheaves, so the blower turns slower than it should and airflow falls off long before the belt finally breaks. Replacing it and setting proper tension is ordinary preventive maintenance, and it is done only after the power is locked and tagged out so the blower cannot start on a call.
Ref QB-2AT9BJSource: NAA CAMT Skill Checks with Answer Key, Air Conditioning Maintenance and RepairReport a problem with this question
17. An older blower motor in an apartment air handler has oil ports at each end bell. What is the correct approach during preventive maintenance?
- A.Oil the ports only once the motor has already begun to squeal loudly
- B.Pack the ports with heavy grease because the oil escapes too quickly
- C.Oil the ports generously every visit so the bearings never run dry
- D.Oil the ports as the equipment maker directs, with power locked out✓ Answer
Sleeve bearings need a specific lubricant in a specific quantity; too much oil runs out of the bearing, collects dust and can reach the windings, while grease will not flow into the bearing at all. Following the equipment maker's instructions with the power locked out keeps the motor safe to reach and correctly served.
Ref QB-HSM4RHSource: NAAEI Certificate for Apartment Maintenance Technicians, HVAC Maintenance and RepairReport a problem with this question
18. At the seasonal changeover inspection, a technician runs the heat in each apartment for the first time since spring. In one unit a brief burning-dust smell clears within minutes and the supply air is warm. What should the technician do?
- A.Replace the heat exchanger before the heating season gets started
- B.Tell the resident to run the heat continuously for a full day now
- C.Shut the gas off at the meter and tag the furnace as unsafe to use
- D.Note the normal first-run smell and finish the inspection checklist✓ Answer
Dust settles on a heat exchanger over a summer of disuse and burns off during the first firing, which is why the smell is brief and then gone while the unit heats normally. That is different from a fuel odor or from soot and a sounding alarm, either of which would call for shutting the appliance down instead.
Ref QB-3A6MGKSource: NAA CAMT Skill Checks with Answer Key, Heating Maintenance and RepairReport a problem with this question
19. A technician suspects an apartment air conditioner has a refrigerant leak and wants to connect a gauge set to the service ports to look at pressures. The technician is not EPA Section 608 certified. What is the correct action?
- A.Do not connect the gauges; refer the unit to a certified technician✓ Answer
- B.Connect the gauges after a supervisor gives verbal permission on site
- C.Connect the gauges but recover any refrigerant into an open container
- D.Go ahead and connect, since only adding refrigerant requires certification
EPA defines a technician to include anyone who attaches or detaches hoses and gauges to measure pressure, so simply gauging a sealed system is regulated work that requires certification. Recognizing that the job has crossed out of routine maintenance and belongs to a certified technician is itself the competency being tested.
Ref QB-JSYEWJSource: EPA Clean Air Act Section 608 technician certification requirementsReport a problem with this question
20. While checking a gas furnace in an occupied apartment, a technician smells gas near the equipment. What is the correct sequence of actions?
- A.Get everyone out without using switches or phones, then call from outside✓ Answer
- B.Light the pilot to burn off the gas that has collected in the space
- C.Use a cell phone in the room to call the utility before leaving it
- D.Turn on the exhaust fan and open windows, then keep working carefully
A gas smell means an ignitable mixture may already be present, and any switch, phone or two-way radio can produce the spark that sets it off. The rule is absolute: do not operate electrical devices, get people out, shut the gas off only if the valve can be reached safely, and make the call from outside the building.
Ref QB-42QRY9Source: NAA CAMT Skill Checks with Answer Key, Heating Maintenance and RepairReport a problem with this question
21. A resident reports the carbon monoxide alarm sounding whenever the gas furnace runs, and the technician sees soot and a yellow flame rolling out at the burner opening. What should the technician do?
- A.Shut the furnace down, ventilate, and call a licensed contractor✓ Answer
- B.Adjust the burner air until the flame is blue and leave it running
- C.Seal the cracked heat exchanger and return the furnace to service
- D.Reset the alarm, change the filter, and let the furnace keep running
Soot, yellow flame and a sounding alarm all point to incomplete combustion, which produces carbon monoxide inside an occupied home. This is a life-safety condition, not a service adjustment: the appliance comes out of service, the space is ventilated, and it stays off until a licensed heating contractor evaluates it.
Ref QB-MHVWJASource: NAA CAMT Skill Checks with Answer Key, Heating Maintenance and RepairReport a problem with this question
22. In a split-system air conditioner that is running normally, what is the state of the refrigerant in the liquid line, after it leaves the condenser and before it reaches the metering device?
- A.A high-pressure vapor
- B.A low-pressure liquid
- C.A high-pressure liquid✓ Answer
- D.A low-pressure vapor
The cycle runs compressor, condenser, metering device, evaporator. The compressor discharges hot, high-pressure vapor; the condenser rejects that heat to the outdoor air and condenses the vapor into a high-pressure liquid, which travels in the liquid line to the metering device. Only after the metering device does the pressure drop, so a low-pressure liquid belongs on the evaporator side, and the evaporator boils it into the low-pressure vapor that returns to the compressor. A high-pressure vapor describes the discharge line before the condenser, not the liquid line.
Ref QB-52346BSource: Vapor-compression refrigeration cycle (compressor, condenser, metering device, evaporator); NAAEI CAMT Air Conditioning moduleReport a problem with this question
23. An HVAC contractor's readings on an apartment air conditioner show an evaporator saturation (boiling) temperature of 40°F and a suction line temperature of 52°F at the outdoor unit. How should the result be described?
- A.12°F of subcooling
- B.12°F of superheat✓ Answer
- C.92°F of superheat
- D.52°F of superheat
Superheat is how far the vapor in the suction line has been heated above the temperature at which the refrigerant boiled: 52°F minus 40°F equals 12°F. It is measured on the vapor (suction) side, while subcooling is measured on the liquid line, so calling the result subcooling mixes up the two sides. Adding the temperatures to get 92°F, or quoting the raw 52°F line temperature, ignores that superheat is a difference from the saturation point. Contractors compare superheat with the manufacturer's target to judge the charge; adjusting the charge is work for a certified technician.
Ref QB-NH89RBSource: Refrigeration definition: superheat = actual vapor temperature minus saturation temperature at that pressure (ASHRAE Handbook—Fundamentals terminology)Report a problem with this question
24. A contractor explains that a system's refrigerant charge was checked by measuring subcooling at the liquid line. What does subcooling describe?
- A.Supply air cooled below its dew point
- B.Coil surface cooled below freezing point
- C.Vapor heated above its boiling point
- D.Liquid cooled below its condensing point✓ Answer
Subcooling is how many degrees the liquid refrigerant leaving the condenser has been cooled below the temperature at which it condensed. It shows how much liquid has built up in the condenser, which is why it is used to judge charge on systems with a thermostatic expansion valve (TXV). Vapor heated above its boiling point is superheat, measured on the suction line. Air cooled below its dew point describes dehumidification, and a coil below freezing describes icing; neither is a refrigerant charge measurement.
Ref QB-62EEBCSource: Refrigeration definition: subcooling = saturation (condensing) temperature minus actual liquid-line temperature (ASHRAE Handbook—Fundamentals terminology)Report a problem with this question
25. A renovation leaves a dozen old window air conditioners that will be scrapped. Under EPA Section 608, what must happen to the refrigerant in them before disposal?
- A.It may be vented outdoors, away from any people
- B.It must be recovered, with the recovery documented✓ Answer
- C.It may be released once the oil is drained out
- D.Nothing, since window units are exempt from the rule
Section 608 of the Clean Air Act prohibits knowingly venting regulated refrigerants, whether indoors or outdoors, and the safe-disposal rules cover small appliances such as window units: the refrigerant must be recovered before the final disposal step, and the scrap recycler must either recover it or get a signed statement that recovery was done. Window units are not exempt, and draining compressor oil does nothing to make release legal. If no certified technician is on staff, the property hires one or uses a recycler that recovers refrigerant.
Ref QB-PHKKWCSource: Clean Air Act §608; 40 CFR 82.154(a) venting prohibition; 40 CFR 82.155 safe disposal of small appliancesReport a problem with this question
26. A technician replaces an old wall thermostat and finds a small sealed glass bulb of mercury inside it. What is the correct way to handle the old thermostat?
- A.Break the bulb and pour the mercury into a sealed jar
- B.Remove the bulb and flush it down a floor drain to dilute it
- C.Keep it intact and send it for universal waste recycling✓ Answer
- D.Toss it in the dumpster, since one bulb is too small to matter
Mercury-containing thermostats are covered by EPA's universal waste rule (40 CFR 273), and many states ban them from the trash, so property staff send them to a recycler or thermostat collection program. Keeping the unit intact matters because a broken bulb releases mercury vapor and creates a spill that needs cleanup. Pouring the mercury into a jar spreads the hazard, the dumpster sends mercury to a landfill no matter how small the amount, and a drain puts it into the sewer system.
Ref QB-72SRGDSource: EPA Universal Waste Rule, 40 CFR 273.4 and 273.13(c) (mercury-containing thermostats)Report a problem with this question
27. On a cold winter morning, a resident reports that the heat pump's outdoor unit stopped its fan for a few minutes while steam rose from the coil, then went back to normal. What is the most likely explanation?
- A.An overheated compressor shutting down on its internal limit
- B.A normal defrost cycle melting frost off the outdoor coil✓ Answer
- C.A failed outdoor fan motor burning and giving off smoke
- D.A refrigerant leak escaping as vapor from the outdoor coil
In heating mode the outdoor coil is the evaporator, so in cold, damp weather it collects frost. The defrost control shifts the reversing valve to cooling mode for a short time and stops the outdoor fan, sending hot refrigerant through the outdoor coil to melt the frost; the steam is that melting ice, and auxiliary heat usually runs to keep the supply air warm. A leak does not produce a visible cloud that ends on its own, a compressor tripping on its limit would not stop just the fan, and a burning motor gives off smoke and an odor rather than clearing in minutes. The technician can explain this to the resident and note the visit; no repair is needed.
Ref QB-QHXW3ESource: Heat pump operation: reversing valve and defrost cycle with auxiliary heat (NAAEI CAMT Heating module; standard heat pump sequence of operation)Report a problem with this question
28. A resident's thermostat calls for heat on an induced-draft gas furnace with hot surface ignition. Which event should happen first in the furnace's normal sequence of operation?
- A.The indoor blower starts and moves air through the ducts
- B.The inducer motor starts and proves the vent is clear✓ Answer
- C.The gas valve opens and gas flows to the main burners
- D.The hot surface igniter begins to glow and heat up
The basic sequence is: call for heat, inducer motor starts and a pressure switch proves the vent is drawing, the igniter heats, the gas valve opens and the burners light, the flame sensor proves flame, and the blower starts after a short delay. The control will not power the igniter or open the gas valve until draft is proven, so combustion gases always have a path out. The blower waits until the heat exchanger has warmed so it does not push cold air into the apartment. If the flame sensor does not prove flame, the gas valve closes and the control retries or locks out.
Ref QB-YZ9EA5Source: Induced-draft gas furnace sequence of operation (call for heat, inducer and pressure switch, ignition, flame proving, blower-on delay); NAAEI CAMT Heating moduleReport a problem with this question
29. In a building with hot-water baseboard heat, the boiler and circulator pump are running, but a top-floor apartment's baseboard stays cold and the resident hears gurgling in the pipes. What should the technician do first?
- A.Shut off the circulator so the water can settle evenly
- B.Raise the boiler's water temperature setting higher
- C.Close the lower-floor valves to push more heat upstairs
- D.Bleed the trapped air at the baseboard bleeder valve✓ Answer
Air in a hydronic system rises to the highest point, and the gurgling tells the technician an air pocket is sitting in the top-floor loop and blocking water flow. Opening the bleeder valve with a container ready until a steady stream of water comes out lets the circulator push hot water through again; afterward the technician checks the boiler pressure gauge, and repeated air problems are referred to a boiler contractor. Hotter water cannot get past an air lock, shutting off the circulator does not remove the air pocket and stops heat to every apartment on the loop, and closing other floors' valves takes heat away from residents without clearing the air.
Ref QB-GHFKV5Source: Hydronic heating basics: air elimination by bleeding baseboard/radiator vents; circulator moves water (NAAEI CAMT Heating module)Report a problem with this question
Other topics in this exam
Practice questions based on the published NAAEI CAMT domains — Essential Trade Skills, Compliance, Facilities Operations, and Professional Development & Collaboration — and on standard trade practice. CAMT and NAAEI are marks of the National Apartment Association; this site is not affiliated with or endorsed by NAA or NAAEI. Code requirements, licensing boundaries and permit rules vary by jurisdiction and revise on a cycle, so none is tested here as a recalled figure — always verify the code having jurisdiction and use a licensed contractor where the work requires one. Confirm current program requirements with NAAEI before testing. About the CAMT credential →